Division 16 - Electrical

Division 16 - Electrical
16.01 Electrical Design and Documentation


     A.   All service entry equipment shall be UL listed for such
          application and AIC rating shall be required for each
          component of the equipment.  Series ratings for fault
          capabilities is not acceptable.

     B.   Calculations shall include, but not be limited to, fault
          current, over current coordination, KVA by switchboard,
          KVA by panel, KVA of lighting, KVA of receptacles,
          voltage drop at feeder/panel during motor start, lighting
          illumination levels, power factor, peake demand, and
          diversity factor.

     C.   Electrical schedules shall include the following
          information:  schedule name, location, mounting, main
          device, bussing, interrupting capacity (integrated
          rating), voltage, phase, connected lighting load,
          connected power load, connected receptacle load, and
          expected demand.  Each circuit shall include the
          following:  circuit number, description of load served,
          wire size, connected load, and circuit breaker size.

     D.   All power, lighting, and distribution panels, switchgear,
          MCG's transformers, and switches (disconnect and
          transfer) shall be labeled with room number, circuit
          number, and panel or device number for the power source
          feeding the device.

     E.   All medium voltage manholes shall be drawn in a fold-down
          detail.

     F.   Typical drawings are to be shown.

     G.   Electrical power and lighting plans shall be drawn on
          separate drawings.

     H.   Performance data for electrical equipment shall be shown
          on the drawings.  This data may also be included in the
          specification but shall be carefully edited for
          conflicts.

     I.   Demolition shall not be shown on the same drawing(s) with
          new work.
     
     J.   All switchboard and panel board legend information shall
          be typed and shall include room numbers for locations of
          loads being served, as well as CB# and panel where device
          receives power.

     K.   For a design-build contract all calculations shall be
          received by the 50% CD submission.

     L.   Labeling nomenclature shall be in accordance with Plant
          Engineering, Department of Physical Plant's requirements.

     M.   Campus color codes for communication, fire, power, and
          CCMS use shall be applied as set forth below.

                    SYSTEM NAME              COLOR
          ____________________________________________________
                    CCMS                     Green
                    Communications           Blue
                    Fire Alarm               Red
                    Security                 Yellow
                    REES                     White

     N.   Operation and maintenance manuals shall be supplied with
          each major piece of equipment.  Wiring diagrams, spare
          parts lists and vendor contact numbers shall be supplied
          as part of these submittals.  Fire alarm O&M manuals
          shall provide a riser, wiring and annunciator diagram.

     O.   The A/E shall prepare and submit for review and approval
          all specifications for all aspects of the work, all
          equipment, and materials for the procurement,
          installation, and execution of the work requisite for the
          complete operable installation. Specifications shall be
          prepared in accordance with Construction Specification
          Institute (CSI) format and shall comply with the latest
          editions of all applicable codes.

16.02 Energy and Energy Analysis


     A.   Energy

          The University regards the reduction of energy
          consumption as an important objective in all University
          facilities.

          To comply with the requirements of this manual, the 
          design shall meet the Energy Performance Index, using the
          procedures detailed in the University Manual in order to
          demonstrate that the design meets the energy performance
          criteria.

          To be fully cost effective, energy conservation measures
          must be given early and careful consideration during the
          design phase of a new construction project.  To ensure
          that energy conservation is given priority status, an
          independent Energy Analyst shall be utilized.  The role
          of this Energy Analyst shall be to:

          1.   Review and coordinate all disciplines within the
               design team to achieve the most optimal energy
               efficient design;

          2.   Review architectural, mechanical, and lighting
               submissions for compliance with energy guidelines
               developed by the University, prior to submission to
               the University;

          3.   Perform energy and life cycle analysis, to
               influence the building design to minimize future
               energy expenditures, and to achieve the
               University's desired energy budget;

          4.   Attend early design meetings to address building
               site, orientation, and shape as factors in energy
               consumption;

          5.   Calculate the projected energy cost of various
               design alternatives, as requested by the
               University;

          6.   Prepare required energy reports;

          In designing for energy conservation, the entire facility
          shall be considered, its site and prevailing climatic
          conditions.  Interactions among these elements as well as
          the facility's energy using systems must be taken into
          account.  Design elements and sub-systems must be
          analyzed to arrive at the most appropriate mix of energy
          conservation measures.

     B.   Energy Analysis

          Any building includes a diverse collection of spaces and
          functions with varying environmental requirements. 
          Therefore, a system that is both efficient and
          functionally responsive shall be developed.  This
          includes conducting a comprehensive Energy Study of the
          building and a cost/benefit analysis of available energy
          saving alternatives.  The following considerations have
          been specifically designated for evaluation.  Other such
          considerations shall be investigated which affect the
          quality of the building environment and the cost of
          operating its system.

          1.   Design variations in the fenestration, thermal
               resistance for the exterior surfaces, and building
               geometries which take advantage of passive energy
               conservation systems.

          2.   Systems selection contingent on life cycle cost and
               compatibility with building needs.  A minimum of
               three different systems are to be analyzed.

          3.   Instrumentation of the building so that the
               building automatic central control systems will
               monitor and control the various components.

          4.   Functional zoning of the building by use and
               exposure.

          At the Design Development submittal stage, provide a
          formal written analysis to include, but not limited to:

          1.   Single line, conceptualized schematic system
               drawings on floor plans.  All HVAC duct work shall
               be drawn double line in plan view regardless of
               scale.

          2.   Heating, ventilating, and air conditioning block
               and zone load calculations.

          3.   Economic cost/benefit study of the system chosen
               and compared to alternatives chosen.
          
          4.   A computer energy analysis of the building system's
               energy consumption, operation, and maintainability
               over a period of not less than five years to
               compare life cycle costs for the various HVAC
               systems.  It is desired to obtain from this
               analysis the projected cost of operation by varying
               hours of use and occupancy in the computer program. 
               One of the following shall be used:

               DOE - 2   Computer Program
               Order:    National Technical Information
                         5285 Port Royal Road
                         Springfield, VA 22161

               Info: 1.  Lawrence Berkley Lab
                         University of Calif.
                         Berkley, CA 94720
                         (415) 486-5711


                     2.  TRACE Computer Program
                         12320 Parklawn Drive
                         Rockville, MD 20852
                         (301) 984-2400

                     3.  E20-II Computer Program
                         Box 4808
                         Carrier Parkway
                         Syracuse, N.Y. 13221
                         (315) 432-6000

This analysis is to show the cost benefit of the systems selected
by having compared selected alternative mechanical systems pre-
approved by the design project manager.
Analysis will be used in systems selections.  ASHRAE approved or
based programs such as Trane Tracer, York Yes III, Carrier OP Cost,
DOE II, Trakload, or approved equal shall be used.

16.03 Electrical Distribution


     MEDIUM VOLTAGE DISTRIBUTION 

     A.   Building electrical service shall be supplied via campus
          13,200 volt distribution system.  All primary connections
          are loop configured and will apply S&C low profile
          outdoor switchgear.
          Medium voltage 15KV feeders consist of 3-1/c, 4/0 AWG,
          EPR, 133% insulated 15KV copper conductors and 1 #1/0 AWG
          bare stranded, tinned copper grounding conductor in each
          set of feeder. All feeders shall be provided from the
          existing electrical manhole to the new medium voltage
          switchgear.  Indicate all cuttings and splices in the
          existing manholes.

     B.   All electrical distribution configuration shall provide
          the highest level of segregation when program documents
          identify distinct tenant space allocations.  Opportunity
          for utility sub-metering shall be considered for
          facilities having auxiliary occupants.
     
     C.   The raceway between service entry equipment and
          transformer secondary or generator shall include
          provision of 50% spares.

     D.   All outdoor enclosures shall be NEMA 4 and accessible
          from all sides.

     E.   Transformers shall be outdoor, oil-filled  units with
          primary fusing via the S&C switchgear.

     F.   All duct bank incorporated in the primary loop
          distribution shall include, as a minimum, 100% spare
          raceways.

     G.   Pre-cast concrete manholes shall be provided as necessary
          to facilitate the installation and as required for
          pulling the conductors as per cable manufacturer's
          recommendations.  The manholes shall not be provided more
          than 400 feet apart.  Use campus standard manhole size
          (see standard details).

     H.   All cables located in manholes shall be labelled
          indicating origination and destination locations. 
          Contact the Department of Physical Plant for exact
          nomenclature.

LOW VOLTAGE DISTRIBUTION

     A.   Service entry disconnecting means shall be one or more
          circuit breakers for services of 400 amps or less.  For
          services greater than 400 amps a single main breaker
          shall be applied.  Fused disconnects are not acceptable.

     B.   The secondary side of transformer shall include provision
          for 100% spare breakers for conduit serving the service
          entry equipment within the building.

     C.   Provide for and show a complete fully circuited building
          power wiring system including service equipment
          switchgear / switchboard, panelboards, transformers,
          disconnect switches (non-fused), motor starters, circuit
          breakers, receptacles, conduits, wires, boxes, and all
          those items requisite for a complete installed and
          operating system for the building including any
          alternates.  All conductive components shall be copper.

     D.   Provide surge protection for each phase at the main
          distribution panel(s).

     E.   All panel boards shall have main circuit breakers.  Main
          lugs only panel boards and plug-in-type circuit breakers
          in the panel boards shall not be acceptable.  Series
          rated circuit breakers and panels shall not be acceptable
          for use and/or for coordination.

     F.   Provide for and show all heating, ventilation, and air
          conditioning equipment with connections, starters, and/or
          disconnect switches as required and in accordance with
          the National Electrical Code.  Provide for and show all
          associated power and control wiring and raceway for a
          complete working system.

     G.   Provide for and show all connections, starters and/or
          disconnect switches, power, and control wiring in
          accordance with National Electrical Code to the equipment
          specified in other sections of the documents.

     H.   All low voltage wires for feeders, branch circuits, and
          control circuits shall be copper conductor, THHN/THWN,
          600 volt insulation, rated at 75  C.  Use of wire smaller
          than #12 AWG for feeder and branch circuits, and #14 AWG
          for control circuits shall not be acceptable.  Feeder and
          branch circuit conductors larger than #10 AWG and all
          control circuit conductors shall be stranded.

16.04 Basic Electrical Materials and Methods


REGULATORY REQUIREMENTS

All work shall conform to the requirements of all authorities
having jurisdiction over this work and latest editions of the
codes, regulations and specifications.

1.1 RACEWAYS

Use only specified raceway in the following locations:

     Indoor and Outdoor Locations:

     1.   Installation in or under concrete slab shall be rigid
          galvanized steel conduit only and/or PVC SCHEDULE 40.

     2.   Exposed outdoor locations:  Only rigid galvanized steel
          conduit shall be used.  Use threaded or raintight
          fittings for metal conduits.

     3.   Wet interior locations:  Rigid galvanized steel conduit. 
          Use threaded or raintight fittings.

     4.   Concealed dry interior locations:  Electrical metallic
          tubing.

     5.   Exposed dry interior locations:  Rigid steel conduit.

     6.   Connections to vibration producing equipments shall be
          liquid tight flexible metallic conduit for exterior and
          wet locations.

     7.   Connections to motors for all locations shall be liquid
          tight flexible metallic conduit.

     8.   The building distribution system with raceway conduits in
          slab shall not be permitted.

     9.   Raceway/conduit in finished areas shall be concealed by
          architectural surfaces.

     10.  For connections for lighting fixtures, VAV Boxes, and
          receptacles, refer to Section 16119 Part 3.

     11.  Use of cable tray shall only be used for distribution of
          telecommunications, Fibre, and COAX.  Cable tray shall
          not be permitted for POWER distribution.


1.02 ELECTRICAL CABINETS AND ENCLOSURES

A.   Hinged Cover Enclosures.

          1.   Construction:  NEMA 250; NEMA Type 1 enclosure in
               dry locations, and NEMA type 4 steel in wet or damp
               locations.

          2.   Finish:  Manufacturer's standard enamel finish.

          3.   Covers:  Continuously hinged, held closed by flush
               latch operable by key or a screwdriver.

          4.   Interior panel for mounting terminal blocks or
               electrical components:  white enamel finish, 14
               gauge steel.

     B.   Electrical Cabinets.

          1.   Construction:  Galvanized steel with removable end
               walls.

          2.   Cabinet Fronts:  Steel, flush type with concealed
               hinge and flush lock; finish in gray baked enamel.

          3.   Cabinet size as required with backboard for
               mounting terminal blocks etc.

          4.   Terminal Blocks:  ANSI/NEMA ICS 4.  Provide ground
               bus terminal block with each connector bonded to
               enclosure.

1.03 LADDER-TYPE CABLE TRAY

     A.   Description:  NEMA VE 1, ladder type tray, as
          manufactured by B-line or approved equal.

     B.   Material:  ASTM A570, Grade 33 for 14 Gauge fittings
          shall have not less than the load-carrying ability of
          straight tray sections.

     C.   Finish:  ASTM A 123, hot dipped galvanized after
          fabrication.  Painted with gray epoxy.

     D.   Inside Width:  Shall be suitable for 30 percent future
          growth.
     
     E.   Inside Depth:  Shall be suitable for 30 percent future
          growth.

     F.   Straight Section Rung Spacing:  9 inches on center.

     G.   Inside Radius of Fittings:  As required.

     H.   Provide manufacturer's standard clamps, hangers,
          brackets, splice plates, reducer plates, blind ends,
          barrier strips, connectors, and grounding straps.


16.05 Emergency Power


     A.   Emergency power for the following systems is required:

          1.   Fire Alarm
          2.   Security
          3.   Emergency Lighting
          4.   Telephone Service
          5.   CCMS
          6.   Other systems as may be needed/identified by the
               University.

          Lighting equipment pertaining to code required
          illumination shall be also supported by an emergency
          generator.
          All mechanical and electrical rooms having disconnecting
          or air handling equipment shall have 50% of connected
          lighting served by an emergency circuit.  All lighting
          shall be switchable at entry to room.
          Where applicable, new loads shall be connected to
          existing generators to maximize the use of existing
          equipment.

     B.   The size of the generator set shell be calculated by A/E
          base upon the connected load include any Alternate plus
          20 percent spare capacity for future expansion.         
          
     C.   Provide for and show a generator set with automatic
          transfer switch, manual by-pass, start/stop control
          system, remote alarm annunciator, battery charger, and
          other accesories for a complete working system. 

     D.   Fuel to power the generator shall be selected on the
          basis of cost and availability with a preference for
          natural gas followed by fuel oil and propane gas.

     E.   Acceptable locations for Emergency Generators:

          1.   SCUB
          2.   Basement or ground floor of building,
          3.   A weather protected enclosure meeting noise
               abatement standards adjacent to building.

          No other locations are acceptable.

     F.   Generator exhaust shall not be discharged in a fashion to
          cause it to enter any building's air handling system or
          into pedestrian walkways.

     G.   Generator rooms must be large enough to enable repairs.
          Access doors must be large enough to permit removal and
          replacement of the generator without having to dismantle
          the generator in any way.

     H.   The generator shall be run for several hours while the
          building is in use and occupied; therefore, the generator
          must be properly exhausted and sound-proofed so as not to
          interfere with the building's usage.

     I.   Overhead lighting, on an emergency circuit, is required
          in the generator room or within the weather protected
          enclosure while the generator is operational.

16.06 Fire Protection System


The following equipment shall be included as part of a
comprehensive system for fire protection in accordance with NFPA
101, Life Safety Code and approved by DAEC.

     A.   A complete multiplex fire alarm system with a control
          panel located in a designated fire protection services
          room, or as specified.

     B.   A textually graphic annunciator in the main lobby areas
          and other locations as designated.

     C.   Standard fire alarm signals, claxon horns and flashing
          lights located throughout the building.

     D.   The connection of the system with the Central Control and
          Monitoring System.

     E.   The use of smoke detectors, magnetic door releases,
          manual pull stations, and HVAC controls where
          appropriate, and as required.

     F.   A complete automatic sprinkler system throughout the
          building with main controls in a designated fire
          protection services room.

     G.   A complete standpipe system (combined with the sprinkler
          system) for fire department use in areas of the building
          with three or more stories and as directed.

     H.   Fire extinguisher cabinets.

The entire system and all equipment is to be designed and/or
specified in accordance with the latest addition of all applicable
codes and standards.

In cases in which sensitive electronic equipment is to be located
within the facility, it will be necessary to design a fire
detection system capable of interrupting the power supply to the
equipment.  Halon or carbon dioxide type suppression systems shall
not be specified.

Coordination with the Department of Physical Plant, through DAEC to
insure conformity of all new fire protection equipment  is
required.

16.07 Lightning Protection


PART 1 - GENERAL

1.01 SCOPE OF WORK

     A.   The Contractor shall furnish all labor, materials,
          equipment and services necessary for the furnishing and
          installing of a complete Lightning Protection System.

1.02 QUALITY ASSURANCE

     A.   Underwriter's Laboratories, Inc. Standards for Lightning
          Protection Systems, UL 96A.

     B.   National Fire Protection Association Code for Lightning
          Protection Systems, #78.

     C.   The Lightning Protection System shall be designed and
          installed by a firm regularly engaged and experienced in
          installing Master Labeled Lightning Protection Systems
          and shall be listed with the Underwriter's Laboratories,
          Inc.

     D.   The Lightning Protection System shall conform to the
          requirements of the Underwriter's Laboratories Inc.,
          Standards for Master Labeled Lightning Protection
          Systems, UL 96A, latest edition and the Master Label
          covering the existing buildings, shall be delivered to
          the Owner on completion of all work.

     E.   The Lightning Protection Installer shall issue a UL
          compliance certification suitable to present and satisfy
          any and all requirements.

1.03 SHOP DRAWINGS

     A.   The Contractor shall submit, for approval, shop drawings
          showing complete details with description of all air
          terminals, air terminal bases, conductors, conductor
          fasteners, splicers, bonding clasps, ground rods, etc. 
          Only shop drawings bearing the stamp of approval of the
          Architect shall be used by the Contractor.

1.04 WORKMANSHIP

     A.   The Contractor shall guarantee all materials and
          workmanship furnished and installed under this section of
          the specifications two years from date of final
          acceptance of the work.  The Contractor also agrees that
          he will, at his own expense, repair and/or replace all
          such defective materials or effective workmanship which
          become defective during the term of this guarantee.


PART 2 - PRODUCTS

2.01 GENERAL

     A.   The system to be furnished under this specification shall
          be the standard product of a manufacturer regularly
          engaged in the production of Lightning Protection Systems
          and shall be the manufacturer's latest approved design. 
          All material specified for this work shall be
          Underwriter's Laboratories, Inc. approved and shall be
          manufactured by Bonded Lightning Protection, Inc.,
          Rockville, Maryland; Thompson Lightning Protection, Inc.,
          St. Paul, Minnesota; Independent Protection Co., Goshen,
          Indiana; or Robbins Lightning Protection Co., Maryville,
          Missouri.

2.02 MATERIALS

     A.   Materials used in connection with the installation of the
          lightning protection system shall be approved for this
          system by the Underwriter's Laboratories, Inc.

2.03 CONDUCTORS

     A.   All conductors shall be bare stranded cable, 28 strands
          of 14 gauge.

2.04 AIR TERMINALS

     A.   Air terminals shall be aluminum, 1/2 inch in diameter
          with tapered points; they shall extend not less than 10"
          above the object they are to protect.

2.05 FASTENERS, CLAMPS, ETC...

     A.   All fasteners, clamps, and connectors shall be bolted
          pressure type and shall be substantial in construction,
          not subject to breakage, shall be of the same material as
          the conductor or of such nature that there will be no
          serious tendency toward electrolytic corrosion in the
          presence of moisture.

2.06 GROUND RODS

     A.   Ground rods shall be 3/4 inches in diameter by 10 feet in
          length, made of copper-clad steel.  The portion of copper
          on copper-clad rods shall be approximately 27% of the
          weight of the rod.  All ground rods shall be equipped
          with Bonded Lightning Protection #107 ground reservoirs
          and shall be driven to a depth of 36 inches below
          finished grade and/or finished floor, minimum.

2.07 TEST WELL

     A.   Provide a 6 inches diameter by 24 inches terra cotta test
          well with steel covers for each ground rod.  Test wells
          shall be installed flush with the finished first floor
          and/or finished grade. Tests wells shall be Bonded
          Lightning #200.  Ground resistance test shall be
          performed on the finished system and the results
          submitted to the University of Maryland.  Grounds
          resistance shall not exceed 10 ohms on completion.


PART 3 - EXECUTION

3.01 INSTALLATION

     A.   The installation of the Lightning Protection System shall
          avoid penetrations of existing building roofs.

16.08 Lighting


     A.   Provide & design the building lighting system layout
          (Interior and Exterior) in conformance with IES
          recommended procedures and foot candle requirements and
          UMCP illumination requirements.    

     B.   Lighting equipment pertaining to code required
          illumination shall be supported by an emergency
          generator.

     C.   All mechanical and electrical rooms having disconnecting
          or air handling equipment shall have 50% of connected
          lighting served by an emergency circuit.  All lighting
          shall be switchable at entry to room.

     D.   Exit signs will be LED type (2 watts or less) with red
          letters on a white or metallic silver background.  All
          fire and building code required lighting will be
          supported via emergency generator.  Battery back-up
          systems are not acceptable.  Any application of battery
          back-up systems to accommodate code egress or other
          concerns, will require written acceptance by the FM.

     E.   Interior luminaires

          All luminaires in general will be 2'x 4' lay-in, troffer
          type fluorescent construction.  Low power ballasts, T-8
          lamps, and tandem wiring to minimize number of ballasts
          shall be specified.  The use of separately switched
          ballasts in three lamp design shall be limited to
          applications mandating specific switched light levels
          that can only be achieved by this method.

          1.   Fluorescent Tube Ballasts for 4' long tubes shall
               conform to the following requirements using ANSI
               Standards:

               1 Lamp
                    Input Watts                   32
               2 Lamp    
                    Input Watts                   52
               3 Lamp
                    Input Watts                   77
               4 Lamp 
                    Input Watts                   101
               
               Following parameters are same for each ballast:

                    UL Listed                     Class P
                    Ballast Factor                Greater than .77
                    THD                           Less than 20%
                    Sound Rating                  A
                    Minimum Start Temperature     0 Degrees F
                    Ballast Type                  Electronic
                                                  Instant Start
                    Warranty                      5 Year - 100%
                                                  replacement
          
          2.   Design applications of 2'x 2' fluorescent fixtures
               that apply "U-Bent" lamps shall not be permitted.

          3.   Design applications of 8 foot fluorescent lamping
               shall not be permitted.  Tandem 4 foot fixtures
               shall be utilized.

     F.   Corridors

          1.   Corridor lighting will be served via dedicated
               circuits with only hallway lighting and one level
               associated with that circuit.  Corridors may be
               served by a 2 lamp system with aluminum reflector
               or a 3 or 4 lamp with standard white reflector. 
               Black reflectors shall be prohibited.

          2.   Corridor lighting of clear alzak aluminum, semi-
               specular, reflectors in a compact fluorescent
               downlighting fixture is preferred.

     G.   Lamping

          1.   Lamping in any compact fluorescent shall include
               twin-tubes.  Quad tubes are not acceptable.  When
               lumen output is greater than that of a single twin
               tube, double twin tube fixtures shall be specified.

          2.   Mercury vapor lamps are not acceptable.

          3.   Incandescent lamping is an unacceptable
               application.  Any application of incandescent
               lamping shall be approved by FM based on program
               requirements of the user.

          4.   A compact fluorescent with a clear alzak aluminum,
               semi-specular reflector using a single or double
               twin tube is the appropriate application.

     H.   Recessed Lighting

          1.   Shall apply compact fluorescent lamping (twin
               tubes) whenever dimming function is not required
               and illumination levels can be achieved.

          2.   Dimming applications shall incorporate 90 watt,
               incandescent halogen type lamps for general 150 PAR
               lamping applications.

               For fluorescent applications, fluorescent dimming
               may be utilized, but each use will be scrutinized,
               because of the high cost of dimming ballasts. 
               Options to change lighting levels via switching
               shall be reviewed.

          3.   Recessed applications involving heights greater
               than 12' ceilings with no dimming requirement,
               shall be metal halide for maximum burning and
               illumination levels.

     I.   Lenses

          1.   Lenses shall be either diffuser type or 3.5" louver
               type.  Shallow parabolic will not be considered
               except in areas designated for general purpose
               computer use where glare is being controlled.

          2.   Parabolic diffusers shall not be used in rest
               rooms, storage rooms, corridors, mechanical rooms
               and housekeeping closets.  Acrylic diffusers are
               acceptable.

     J.   Exterior luminaires

          1.   Outside street lighting, walkway and building
               lighting shall incorporate the Guardco campus
               standard fixtures or approved equal with metal
               halide lamping.  Existing campus poles shall be
               Corten weathering steel with tapered square
               construction.  If unavailable, acceptable pole
               substitutes include, baked enamel on aluminum or
               fiber glass with a finish (color) to match existing
               poles. This determination requires prior approval
               of FM on a project-by-project basis.  Parking lot
               and walkway coverage shall be documented by vendor
               produced lighting submission as part of design
               package.

          2.   Exterior lighting and parking garage lighting shall
               be enabled by a central contactor configuration
               with a central photoeye operating with parallel
               manner with time clock control; 7 days/24 hours
               time clock; and hand-off-automatic switch (HOA
               switch) and shall operate in such a manner that the
               photo-cell shall turn the lights "ON" at sunset,
               time-clock shall turn the light "OFF" at a pre-set
               time and HOA switch shall have the manual override
               capability to turn the lights "ON" and "OFF" as
               needed. 

          3.   Security lighting shall be supplied for building
               perimeter via wall pack construction for a metal
               halide fixture.  All light fixtures shall be
               centrally switched via a contactor on single
               photoeye control with time clock in parallel
               operation.

16.09 Security Egress for Individuals with Disabilities


     Currently, many facilities that have handicap door openers do
     not have the electronic panic bar.  The handicap door opener
     is activated by the handicap door switch.  During the day the
     door is unlocked and the opener can operate without
     resistance.  The door is locked at night.  When the door is
     locked and the latch prevents the door from opening. 
     Therefore, when the handicap switch is pressed, the door does
     not open.  This condition traps individuals with disabilities
     in the building.

     To alleviate this problem, the following design criteria has
     been established:

     A.   Install an electric panic bar on each door equipped with
          a handicap door opener.

     B.   Interface the door opener with the electric panic bar.

     Reference attached specifications Power Supply
     with delayed relocking module and electric latch retraction)
     and drawings.  In addition, reference
     Section 8., Finishes and Windows (Hardware) and Section 16.,
     Electrical and (Security Guidelines).
Electric Latch Retraction (TIF Format)
Handicap Door System Drawing 9510-03 (TIF Format)
Handicap Door System Drawing 9510-4 (TIF Format)

16.10 Security Guidelines


     A.   All security measures and systems shall be coordinated
          through the Director of Operations and Maintenance, Loss
          Prevention Division (LPD), Police Department and
          incorporate the following:

          1.   Doors

               a.   All entrances shall have an alarm/access
                    control system connected to LPD's main
                    computer.  Each door shall be equipped with
                    either an alarm, a card reader, electric
                    locking devices, and any other necessary
                    equipment to operate the system.  Access shall
                    be controlled by a computer coded card. 
                    Designated doors can be locked or unlocked
                    from the main computer at LPD. (Also Reference
                    Section 16. Security Egress System for
                    Individuals with Disabilities.)

               b.   All exterior doors to be provided with conduit
                    and wiring for future installation of
                    automatic door operators and a card access
                    system.

               c.   Pairs of exterior doors shall have removable
                    mullions for improved security.

               d.   Any required second means of egress shall
                    accommodate wheelchair users.

               e.   All exterior doors which are designated as
                    "EXIT ONLY" shall be installed without
                    hardware on the exterior.

               f.   Service and rear entry doors shall be as
                    entry-proof as possible.  All doors shall have
                    hinge pins which are not exposed to public
                    areas/exterior.

               g.   Garage, service, and rear entry doors are to
                    be as entry-proof as possible.  They should be
                    constructed of heavy-duty construction with
                    locking systems which provide an appropriate
                    degree of security.

          2.   Security Alarm System

               a.   Alarm system controls shall be by Moose
                    Products; access control equipment shall be by
                    Northern Computers; other devices to be by
                    approved vendors per LPD.

               b.   All security alarm equipment and access
                    control system equipment shall be installed in
                    an independent Security Closet.  LPD shall
                    provide exact requirements for location and
                    required electrical service.

          3.   Long corridors should be avoided.

          4.   Rest rooms and stairwells should not be separated
               from areas of high usage.

          5.   Different units within the facility shall be
               separately securable without interfering with
               required egress routes from the building.

          6.   Ground floor windows are discouraged.  If
               installed, ground windows shall be constructed to
               prevent easy entry into the building.

               Surface materials or windows which can be easily
               vandalized should be avoided.  In the event other
               criteria dictates the requirement for operable
               windows, methods for securing these windows are to
               be provided.  Methodology for securing operable
               windows is to be coordinated with the Office of
               Loss Prevention.

          7.   New or expanded stairwells and elevators must
               utilize public spaces for access and egress. 
               Elevators or stairwells should not allow access
               directly into private office areas which would
               jeopardize security to the area.
     
     B.   All departmental and administrative offices should be
          equipped with heavy duty locksets with anti-friction
          latch bolts approved by the University Lock Shop.

     C.   For security camera and security camera equipment
          specifications see the Table of Contents.

16.11 - TELECOMMUNICATIONS SYSTEMS (April 28, 2000)


PART 1 GENERAL 1.01 REFERENCE REQUIREMENTS The provisions of the General Conditions, Special Conditions, Program Requirements and Division 1, General Requirements, apply to the work of this Section. 1.02 SECTION INCLUDES A. Telecommunications service entrance. B. Premises wiring system. C. Broadband type cable video system. 1.03 RELATED SECTIONS A. Shop Drawings, Product Data and Samples B. Product Record Documents C. Cast-In-Place Concrete D. Painting E. Wiring Materials and Methods F. Outside Power Transmission and Distribution 1.04 REFERENCES A. Building Industry Consulting Services International (BICSI), Telecommunications Distributions Methods Manual, Eighth Edition. B. EIA/TIA-569 - Commercial Building Standard for Telecommunications Pathways and Spaces. C. EIA/TIA-TSB67 - Transmission Performance Specifications for Field Testing of Unshielded. Twisted Pair Cabling Systems, October 1995. D. EIA/TIA- Electronic Industries Association/Telecommunications Industry Association (EIA/TIA) 568A-Commercial Building Telecommunications Wiring Standards. E. TSB72 - Centralized Optical Fiber Cabling Guidelines, October 1995. F. EIA/TIA-TSB75 - Additional Horizontal Cabling Practices for Open Offices G. International Standards Organization/International Electrotechnical Commission (ISO/IEC) DIS 11801, January 6, 1994. H. Underwriters Laboratories (UL) Cable Certification and Follow Up Program. I. National Electrical Manufacturers Association (NEMA). J. American Society for Testing Materials (ASTM). K. National Electric Code (NEC). L. Institute of Electrical and Electronic Engineers (IEEE). M. UL Testing Bulletin. N. American National Standards Institute (ANSI) X3T9.5 Requirements for UTP at 100 Mbps. O. Lucent Technologies SYSTIMAX SCS Zone Cabling Guidelines for High 5 Products, Latest Issue. P. Lucent Technologies SYSTIMAX Structured Cabling Systems, Performance Specifications, Latest Issue. Q. Lucent Technologies SYSTIMAX Structured Cabling Systems, Components Guide, Latest Issue. R. Lucent Technologies Generic Specifications: Fiber Optic Outside Plant Cable, Latest Issue. 1.05 QUALITY ASSURANCE A. Contractor shall install work in accordance with the BISCI Telecommunications Distributions Methods Manual. B. Contractor shall install work in accordance with the Lucent Technologies Systimax SCS Guidelines. 1.06 SUBMITTALS A. Before the installation of any wire or equipment, Contractor shall submit shop drawings and product data under provisions of "Shop Drawings, Product Data and Samples" for University approval.(April 28, 2000) B. Contractor shall indicate installation details, cable routing, system configuration, closet identification and outlet numbering on all shop drawings. C. Contractor shall submit all appropriate product data for each component. D. Contractor shall submit manufacturer's installation instructions. 1.07 PROJECT RECORD DOCUMENTS A. Contractor shall submit record documents. B. Contractor shall accurately record location of service entrance conduit, termination backboards, outlet boxes, messenger cable raceways and cable trays, pull boxes, and equipment boxes on 3.5-inch floppy diskettes using AutoCad 14 or latest version. (April 28, 2000) C. Contractor shall document the cable plant and associated equipment installation in accordance with Parts 3.19, 3.20, and 3.21 in this Section. 1.08 QUALIFICATIONS A. Installation of all inside wire, equipment, terminations and associated services shall be performed by Lucent Technologies or a company that is currently a Lucent Technologies Authorized Systimax Certified Structured Cabling System (SCS) Value Added Reseller (VAR) in good standing; and has a minimum of (5) years of experience on similar SCS systems. Prior to the final selection of the telecommunications sub-contractor, the main contractor shall submit its choice for telecommunications sub-contractor for the University's approval. B. Installation of wire, equipment, terminations and associated services with respect to outside plant cabling shall be performed by Lucent Technologies, Business Communications Systems (BCS) Distribution Technology division solely. C. The company specializing in supplying the products specified in this Section shall have a minimum of three (3) years experience distributing such supplies, and shall be duly authorized by the product manufacturer. 1.09 MAINTENANCE SERVICE Contractor shall furnish warranty of Systimax products, applications, and workmanship for no less than 15 years from the date of acceptance by the University. All other non- Systimax products and workmanship shall carry warranties equal to or greater than the Systimax warranty from date of acceptance by the University 1.10 DEFINITION—STRUCTURED CABLING SYSTEM Structured Cabling Systems, Henceforth referred to as “SCS,” wiring is defined as all required equipment and cabling including hardware, termination blocks, cross connect wiring, patch panels, telecommunications outlets, UTP and fiber lightguide cable installed and configured to provide computer data and voice connectivity from each data or voice device to the network file server or voice network/ switch designated as the service point of the local area network. PART 2 - PRODUCTS 2.01 TELEPHONE TERMINATION BACKBOARDS A. The Contractor shall install 3/4-inch fire resistant plywood with Class A surface in all communications rooms (BDF and IDFs). B. Termination backboards shall cover entirely, to a height of 8 feet, all walls within a communications room (BDF and IDFs) C. Minimum backboard size shall be 4’ X 8’ unless otherwise approved by the University 2.02 STATION COPPER CABLE A. All unshielded twisted pair (UTP) station copper cable supporting voice communications requirements, as well as Emergency, Courtesy and Pay Telephones shall be Lucent Technologies XX61 (where XX is either 10 or 20 depending on insulation type), and shall meet Category 5 performance specifications along with the following technical specification: Gauge: 24 AWG Insulation: PVC (1061) or ECTFE (2061) Outside Diameter: 0.17 in (4.3 mm) Maximum DC Resistance: 28.6 Ohms/1000 ft. Nominal Mutual Capacitance: 14 nF/1000 ft @ 1 kHz Attenuation: 6.3 dB/1000 ft @ 1 MHz Characteristic Impedance: 100 Ohms +/- 15% @ 1-25 MHz B. All UTP station copper cable supporting data communications requirements shall be Lucent Technologies XX71 (where XX is either 10 or 20 depending on insulation type), and shall meet the following technical specifications: Gauge: 24 AWG Insulation: PVC (1071) or Teflon(2071) Outside Diameter: 0.22 in (5.6 mm) Maximum DC Resistance: 29 Ohms/1000 ft Nominal Mutual Capacitance: 15 nF/1000 ft @ 1 kHz Attenuation: 2.2 dB/1000 ft @ 1 MHz C. The cable sheath color for the UTP voice communications cabling specified in 2.02A above shall be different from the cable sheath color for the UTP data communications cabling specified in 2.02B above. D. All copper cable and jumpers shall conform to the REA color guide meet NEC article 725-38, 3 (B) 1, 2 and 3. 2.03 RISER COPPER CABLE A. All UTP riser copper cable supporting voice communications requirements shall be standard 24 gauge, paired dual, semi-rigid PVC skin over foamed PE, Lucent Technologies ARMM XXX- R6060 (where XXX is the number of pairs), and shall meet the following technical specifications: Gauge: 24AWG, solid copper conductor, twisted pair DC Resistance: 25.5 Ohms/1000 ft Mutual Capacitance: 16mF/1000 ft Characteristic Impedance: 100 Ohms +/-15% @ 1-16MHz Attenuation: 7.2 dB/1000 ft @ 1 Mhz; 32dB/1000 ft @ 16MHz B. All UTP riser copper cable supporting data communications requirements shall be solid copper conductors, 24 AWG, paired, dual- insulated, Lucent Technologies 1061 25 pair cable and shall meet Category 5 MPS performing specifications as well as technical specifications as follows: Gauge: 24AWG, solid copper conductor, twisted pair DC Resistance: 28.6 Ohms/1000 ft Mutual Capacitance: 14 pF/1000 ft Characteristic Impedance: 100 Ohms +/-15% @ 1-100MHz Attenuation: 6.3 dB/1000 ft @ 1 Mhz; 67dB/1000 ft @ 100MHz 2.04 UNDERGROUND COPPER CABLE The underground copper cable supporting voice and data communications requirements shall be 24 gauge, paired, dual- insulated with foam skin and plastic, flooded by FLEXGEL filling compound, Lucent Technologies GDPPW, and shall meet the following technical specifications: Gauge: 24 AWG, solid copper conductor DC Resistance: 27.3 Ohms/1000 ft Mutual Capacitance: 15.7 nF/ft @ 1kHz Characteristic Impedance: 100 Ohms Attenuation: 6.4 dB/1000 ft @ 1 MHz 2.05 CABLE PROTECTORS FOR COPPER CABLE A. For all pairs, Contractor shall install three-element gas protector modules, Lucent Technologies 4B1-EW, containing silicon avalanche on both ends. B. Contractor shall supply and install Lucent Technologies 195A-type multi-pair Protector panels in BDF and MDF. (April 28, 2000) 2.06 FIBER OPTIC CABLE A. For multimode fiber, Lucent Technologies ACCUMAX LGBC- XXXD-LPX (indoor applications) where XXX is the strand count or Lucent Technologies DSX LXE (outdoor applications) cable, and shall meet the following technical specifications. Core Type: Graded Index Core Diameter: 62.5 (+/- 6) microns Core Eccentricity: 1.5% Nominal - 7.5% Max.Core Ovality: 4% Nominal- 20% Max. Cladding Diameter: 125 (+/-2) microns Cladding Non-Circularity: 2% Maximum Coating Diameter: 245 (+9/-13) microns Refracting Index Delta: 2.0% (+/- .3%) Numerical Aperture: 0.29 Bandwidth Windows: Dual-850 nm & 1300 nm Maximum Attenuation: 3.5 dB/km @ 850 mm 1.5 dB/km @ 1300 mm Typical Bandwidth: 400 Mhz/km @ 850 mm 500 Mhz/km @ 1300 mm Maximum Field Loss: 0.5 dB B. For singlemode fiber, Lucent Technologies ACCUMAX LGBC-XXXD-VRX (indoor applications) where XXX is strand count, or Lucent Technologies 4DNX (outdoor applications) cable, and shall meet the following technical specifications. Core Diameter: 8.3 (+/- 6) microns Core Eccentricity: 1.5% Nominal- 7.5% Max. Core Ovality: 4% Nominal- 20% Max Cladding Diameter: 125 (+/- 2) microns Cladding Non-Circularity: 2% Max Coating Diameter: 245 (+9/-13) microns Refracting Index Delta: 2.0% (+/- .3%) Numerical Aperture: 0.29 Maximum Attenuation/km: 1.0db @ 1300nm .75db @ 1550nm C. All optical fiber cable used shall have the following physical characteristics: Cable Core: Building interior: Air core Building exterior: Filled core stable from -40F to +140F Cable Composition: Building Interior: station: (plenum) OFNP Flouropolymer jacket (non-plenum) OFNR PVC jacket riser: OFNR PVC jacket Building exterior: Non-metallic dielectric Cable Strength: Maximum pulling tension-600 lb. Minimum Bend Radii: (<30% max. pull tension) 10 times cable diameter (>30% max. pull tension) 20 times cable diameter Fiber Identification: Color coding system adequate to unambiguously identify each fiber. See paragraph 3.16 in this Section. The words “Fiber Optic Cables” shall be imprinted on cable no more than one meter apart. 2.07 OPTICAL FIBER TERMINATIONS A. All multimode optical fiber cable installed shall be terminated with a split-ferrule alignment sleeve and a precision ceramic tip. All multimode optical fiber connectors shall meet the following technical specifications: Connector Type: ST (April 28, 2000) Fiber Outside Diameter: 125 microns Nominal Loss Repeat: < 0.2 dB per 100 reconnects Axial Load Minimum: 35 Pounds Temperature Stability: +0.1 dB Maximum from -40 C to 75 C B. All single mode optical fiber cable installed shall be terminated utilizing a split-ferrule alignment sleeve and a precision ceramic tip. All single mode connectors shall meet the following technical specifications: Connector Type: SC Fiber Outside Diameter 125 Microns Loss Repeat: < 0.2 dB per 1000 reconnects Axial Load, min. 30 pounds Temperature Stability: -40 C to 85 C 2.08 OPTICAL FIBER PATCH CORDS A. Contractor shall provide multimode optical fiber patch cords. The multimode optical fiber patch cords shall be Lucent Technologies ML2SC-SC-XX, and shall meet the following technical specifications: Number of fibers: 2 Approximate loss, mean, variance 0.1, 0.1 Minimum bandwidth: 160 MHz-km @ 850 nm B. Contractor shall provide single mode optical fiber patch cords. The single mode optical fiber patch cords shall be Lucent Technologies MS2SC-SC-XX, and shall meet the following technical specifications: Number of fibers 2 Approximate Loss, mean, variance 0.1dB, 0.7dB 2.09 CONNECTING BLOCKS A. All UTP voice copper cable shall be terminated on miniature, high- density, modular Lucent Technologies 110AW2- XXX, where XXX indicates pair capacity, connecting blocks. B. All optical fiber cable in all Building Distribution Frame (BDF) and (IDF) Intermediate Distribution Frame rooms shall be terminated in Lucent Technologies LST1A-48DC/2.5 Lightguide termination shelf and associated equipment. (April 28, 2000) C. All optical fiber cable connencting the BDF to the Fiber Hub Room (designated by the University) shall be terminated in Lucent Technologies LST1U-72 termination shelves at each end. D. All data Category 5E cable shall be terminated on miniature, high-density, modular Lucent Technologies 110 AW2-xxx, where xxx indicates pair capacity, connecting blocks. (April 28, 2000) 2.10 EQUIPMENT RACKS 19" X 84" standard equipment racks shall be utilized for termination of all data outlets and fiber optic terminations in the (IDF) rooms. Sufficient space shall be provided for installation of networking hardware. 2.11 INTRABUILDING COAXIAL CABLE All intrabuilding coaxial cable in the new facility supporting video communications requirements shall be RG-11/U Belden 89292, and shall meet the following technical specifications: Gauge: 14 AWG solid bare copper covered, .064 in Outside Diameter: 0.348 in (8.84 mm) Shields: Duofoil + 61% tinned copper braid Insulation: Black tint Teflon jacket Nominal DC Resistance: 2.5 Ohms/1000 ft Nominal Mutual Capacitance: 16.5 pF/ft @ 1 kHz Attenuation: .15 dB/100 ft @ 1 MHz Characteristic Impedance: 75 Ohms @ 1 MHz 2.12 INTERBUILDING COAXIAL CABLE All interbuilding coaxial cable in the new facility supporting video communications requirements shall be P-3-75- 500JCASS, and shall meet the following technical specifications: Gauge: 0.111 in. (2.82 mm) nom. Outside Diameter: 0.560 in. (14.22 mm) nom. Outer jacket of medium density polyethylene, solid aluminum sheath and Migra-Heal compound between jacket and sheath Nominal DC Resistance: 0.37 Ohms/1000 ft Attenuation: 0.66 dB/100 ft @ 83 MHz Characteristic Impedance: 75 Ohms @ 1 MHz 2.13 VIDEO SYSTEM PARTS AND ACCESSORIES A. Contractor shall install self-terminating video outlets with a built-in 75 Ohm resistor and a connector actuated switch that automatically terminates the line when a push-on cable connector is removed. B. Coaxial cable equipment: The following equipment of University approved equivalent shall be used: Line extender: CCOR LAN-100-2rv Pads (attenuators) for CCOR LAN-100-2rx: PB-0 PB-12 PB-3 PB-15 PB-6 PB-18 PB-9 PB-21 Pads for Line Extender: Forward dbmv of cable @ 450 MHz Eq-450-3 2.5 Eq-450-5 6.2 Eq-450-8 9.9 Eq-450-11 13.8 Eq-450-13 17.3 Eq-450-15 20.9 Splitters and Directional Couplers: Insertion Loss Type Tap Value @ 450 MHz Jerrold SSP-3 4.4 Jerrold SSP-6367.9, 7.9 4.4 Jerrold SSP-7 7.8 2.5 Jerrold SSP-9 10.0 1.8 Jerrold SSP-12 12.8 1.5 Jerrold SSP-16 16.3 1.2 Full Feature Taps: Insertion Loss Type Tap Value @ 450 MHz Jerrold FFT8-14 14.2 4.3 Jerrold FFT8-17 17.8 1.8 Jerrold FFT8-20 20.0 1.2 Jerrold FFT8-23 22.5 1.0 Jerrold FFT8-26 26.1 0.8 Jerrold FFT8-29 29.2 0.6 Connectors and Other Accessories: Gilbert Parts: Pin Connector: GRS-500-CH-DU-03 Power Blocking Ks-F: GF-625-CH-DCB Chassis-Chassis Connector: G-KS-KS-M Right Angle Connector: GP-90-S Splice Connector: GRS-500-SP-DU-03 Teflon RG-11 Connector: GF-11-300p-388 F-type terminators: GTR-59-s D-Rings for Mounting Equipment: Type Inside Dimension Outside Dimension Graybar GB 13a 1-7/8" 4-7/8" Graybar GB 13b 3-1/8" 6-1/8" Crimping Tool: Teflon RG-11 Crimper: HCT-775 Testing Equipment: RF Signal Strength Meter: Wavetek SAM III or approved equal must be used for testing. 2.14 OUTLET BOXES A. All outlet boxes supporting voice/data communications requirements shall be double-gang, four (4) inch square, be three (3) inch deep minimum galvanized steel boxes. B. All outlet boxes supporting video communications requirements shall be single gang, four (4) inch deep minimum galvanized steel boxes. 2.15 VOICE/DATA OUTLETS AND COVER PLATES A. The outlet assembly to support voice only communications requirements shall be one (1) eight (8) position eight (8) wire modular RJ45 outlet. Lucent Technologies MPS100BH-246 is acceptable. B. The outlet assembly to support voice/ data communications requirements shall be two (2) eight (8) position, eight (8) wire modular RJ45 outlets. The dual RJ45 receptacle shall consist of two (2) RJ45 outlets. The standard voice/ data outlet is to be mounted in a vertical position with one RJ45 non-keyed outlet labeled “Voice” (Lucent Technologies MPS100BH-246) and one RJ45 outlet marked “Data” (Lucent Technologies MGS200BH-112) below. C. Voice/ data/ video outlets shall be one (1) RJ45 non keyed outlet labeled “voice” (Lucent Technologies MPS100BH-246) and one (1) RJ45 outlet marked “data” (Lucent Technologies MGS200BH-112) and one (1) M81C-246 video F81 coaxial video module. D. The "pin out" wiring assignment for the 4-pair UTP copper cable for both voice and data shall be consistent with the TIA/EIA T568B Commercial Building Telecommunications Wiring Standard. E. All outlet plates shall be Lucent Technologies M28A modular faceplates with M20AP modular covers filling unused portals. 2.16 HORIZONTAL DISTRIBUTION CABLE MANAGEMENT SYSTEM A. Cable Tray Pathways 1. Cable tray is required in all areas where horizontal cabling bundle quantity (copper, optical fiber and coax) exceeds 40 wires. 2. Cable tray for telecom applications shall be Cablofil Incorporated EZTray or an approved equivalent, and shall adhere to the following dimensional guidelines: Dimension EZTray Part# Bundle Quantity 4"D X 12" W CF 105/300EZ Less than300 4"D X 18" W CF 105/450EZ 300- 450 4"D X 24" W CF 105/600EZ In excess of 450 3. Cable tray shall be installed to the specifications of the manufacturer. B. J-Hook Pathways 1. J-hooks shall be utilized in all areas where bundle quantity is between 10 and 40 cables 2. All j-hook pathways shall be provided with a center hung, triple tiered, six hook cable support system with a maximum spacing specified as not greater than four (4) feet. Contractor shall submit samples and cutsheets on proposed solutions. 2.17 DUCTBANK INNERLINERS A. Innerliners are required. Contractor shall furnish Pi- Mar PVC conduit manufactured by Pyramid Industries Inc., in each section specified. The innerliner shall conform to the following University color code indicating type of media routed in the innerliner: MEDIA INNERLINER COLOR SIZE Fiber Orange 1" Copper Black 1.5" Coaxial Yellow 1.5" 2.18 CABLE LUBRICANT A. Cable pulling lubricant, Ideal Yellow 77 or a University approved equal, shall be utilized when pulling all cable. 2.19 CASES AND SPLICES A. All Building Entrance Splice Cases shall be Lucent Technologies type 2000 series closure and accessories. B. All outside plant (OSP) Cable Splice Cases shall be Preformed Line Products Stainless Steel with Filling Flange and must be filled with a University Approved re-enterable encapsulant. C. All entrance cases in the Patuxent Building, Building 010 shall be Lucent Technologies Cable Rearrangement Facilities. 2.20 FIRESTOPPING A. Contractor shall provide firestopping protection that shall meet NFPA Life Safety Code #101, 6-2.3.6, "Penetrations and Miscellaneous Openings and Fire Barriers" and the NEC 300.21 "Fire Stopping" regulations and standards. B. All vertical penetrations consisting of conduit, sleeves, or chases shall be firestopped at the bottom of the penetration. C. All horizontal penetrations consisting of conduit, sleeves of chases shall be firestopped on both sides of the penetration. D. Individual cable penetrations in plenum air return areas not enclosed in conduit shall be firestopped. E. Openings made in concrete floors shall be firestopped using a tested system. Thickness or depth of firestop materials shall be as recommended by the material manufacturer and backed by formal ASTM E-814 tests. F. Plenum air return ceiling penetrations for conduit and cables shall be sealed with a system appropriate for the substrate and level of protection required. G. All metal conduits designed for communications with or without wire/cable inside shall be firestopped to restrict transfer of smoke. 2.21 ELEVATOR PHONE A. The Contractor shall coordinate with the Elevator Contractor to install the following campus approved Elevator Phone: Manufacturer Description Stock No. Talk-A-Phone Co. Hands-free Phone EPT-100E 5013 North Kedzie Ave. programmed to use Chicago, IL 60625 campus circuit 312-539-1100 assurance equipment 2.22 OUTDOOR EMERGENCY PHONE A. The Contractor shall coordinate with the General Contractor to install the following campus approved Emergency Phone: Manufacturer Description Stock No. Code Blue Corporation Vandal resistant security NE922K 40 E. 64th Street unit with speakerphone with Holland, MI 49422-9322 keypad and University of MD 616-392-8296 software, blue light, and strobe. **** Wall Mount for Garages and CB718K w/ other locations as specified U of MD by the University. Code Blue II Software with 12 button keypad and University of Maryland software PART 3 - EXECUTION 3.01 SYSTEM DESIGN A. The cabling system to support voice, data, and video requirements has been designed in accordance with BICSI, EIA/TIA, NFPA, NEC, Lucent Technologies, IEEE, and FCC communications. B. The proposed cabling system has been designed and shall be installed in a manner that provides mechanical integrity and symmetry for the cabling media and any associated frames and racks and which also furnishes ease of access and suitability for future rearrangements and changes. C. The transmission media shall be installed through a network of cable trays, conduit, sleeves, and chases and interconnect the various rooms and floors of the building. D. Telecommunications Closet Design Requirements (BDF and IDFs) 1. BDF a. BDF shall be located on lowest level of building. b. BDF shall be at least 200 square feet. c. BDF shall have neither width or depth less than 12 feet. d. Two (2) 20 ampere dedicated circuits with one (1) duplex receptacle each. 2. IDF(s) a. Each floor with telecommunications outlets must include at least one (1) IDF. b. IDF(s) must be placed such that the longest station run is less than 90 meters from outlet termination point to the cross connect. c. IDF(s) shall be sized as follows: # of Stations Minimum Closet Size Minimum Width/ Depth less than 60 50 square feet 6 feet 60-100 100 square feet 8 feet Over 100 120 square feet 10 feet d. IDF(s) shall be “stacked" one above the other. e. 4" conduits (or sleeves where appropriate) shall be installed to accommodate current needs plus 100% growth. f. Office grade HVAC shall be provided. g. Two (2) 20 ampere dedicated circuits with one (1) duplex receptacle each. E. Determination of station quantities—quantity and placement of outlets, as well as outlet labeling assignments, shall be shown on the floor plans. F. Determination of minimum station quantities: 1. General Office Space One (1) outlet per 70 square feet 2. Faculty Office Space One (1) outlet per 70 square feet 3. Conference Room One (1) outlet per wall one (1) e/w CATV outlet 4. Computer Laboratory Space One (1) outlet per 30 square feet 5. Scientific Laboratory Space One (1) outlet per 140 square feet 6. Server/ Computer Room One (1) outlet per 20 square feet 7. Standard Classroom Two (2) outlets in front of classroom one (1) e/w CATV outlet. 8. Multimedia Classroom Four (4) outlets in front of classroom (1) e/w CATV. One (1) outlet for each permanent seating area. 3.02 FORBIDDEN WORK A. Other than the entrance splice, no cable splices shall be allowed within buildings. B. Aerial cable construction shall not be permitted. 3.03 EXAMINATION A. Contractor shall verify that surfaces are ready to receive work. B. Contractor shall verify that field measurements are as shown on the CDT's Construction Drawings approved by the University. C. The beginning of installation means installer accepts existing conditions. 3.04 INSTALLATION OF BACKBOARDS A. All termination backboards in the BDF and IDFs shall be finish painted with durable white enamel prior to installation of any communications equipment. (April 28,2000) B. All backboards shall be supported as specified. (April 28,2000) C. All backboards shall be marked with the legend "COMM" under the provisions. (April 28,2000) 3.05 CABLE PULLING Contractor shall utilize cable pulling lubricant for all pulls in conduit ducts or innerliners. Not less than three (3) gallons per kilometer shall be used. 3.06 COORDINATE WITH OTHER TRADES A. Cable routing shall be designed and installed so that cabling and associated equipment does not interfere with the operation or maintenance of any other equipment. No wiring shall be hung, tied to, or supported from anything other than telecommunications raceway or the building structure. B. All cable in accessible spaces shall be designed and installed for easy access. Cable paths above suspended ceilings, mechanical rooms, closets, etc. shall not be blocked or covered in any way that would impede the addition of cable in the future. 3.07 CONDUIT INSTALLATION A. To support voice and data communications requirements, Contractor shall install one (1) inch conduit from the outlet box stubbed into the accessible ceiling. Contractor shall conform to the Conduit Installation Schedule in Section 16100 for selection of appropriate conduit type. All telecommunications wiring shall be concealed in conduit or in the ceiling. B. Conduit sleeves shall be four (4) inch trade size minimum. Sleeves shall be Rigid Galvanized Steel for penetrations of concrete slabs, concrete walls, and CMU walls. Sleeves for penetrations of stud walls shall be EMT. All sleeves shall be rigidly installed using appropriate fittings and all masonry penetrations shall be grouted. Sleeves shall project a minimum of six (6) inches beyond wall or floor surface. All penetrations of fire rated construction shall be firestopped with fire- stopping as specified in Part 2.16 of this Section to equal or exceed fire rating of the penetrated material. Sleeves for penetration of walls and floors shall have one hundred percent (100%) spare capacity, and shall be firestopped as per code. C. Any section of conduit containing two (2) 90-degree bends, a reverse bend, of having length greater than one hundred (100) feet shall have an accessible pullbox. All conduits with less than a 50% fill ratio shall have a 3/32- inch polyethylene pull cord approximately secured at each end. D. No oval or square conduit fittings shall be permitted. No screw type fittings shall be permitted. E. All metallic conduit and raceways shall be appropriately grounded as specified in the National Electric Code. F. Supports and fasteners shall be used to hold all cables, conduits, and trays firmly in place. Supports and fasteners shall be used such that they provide an adequate safety factor. All conduit/cable trays shall be supported from the building structure and not from any other ductwork, pipes, ceiling tiles, or equipment. G. Where cable trays or conduit are not provided (especially between the stubbed out conduit and the nearest cable tray). Kindorf lay-in pipe hangers, or a University approved equal shall be installed. The lay-in pipe hanger shall be attachable to a floor slab through the use of a pre- threaded lead insert which is suitable for installation of a 3/8-inch "all-thread" rod in a predrilled 1/2-inch hole. The threads of the closure bolt on the pipe hanger shall be covered by 3/8-inch copper or aluminum tubing to protect the cabling sheaths. H. Cables placed in hangers in the plenum ceiling area shall be routed high and away from all other electrical and mechanical systems so as to avoid contact with light fixtures, ventilation ducts, sprinkler systems or plumbing piping, motors, or any other electrical devices. The cable shall not be run in parallel with any high voltage electrical wiring. The maximum separation between support points for all cabling shall be eight (8) feet. Lay-in pipe hangers shall be installed so as to accommodate these maximum distance spacings. Hangers shall be installed at directional bend points so as to provide a maximum bend angle of 45 degrees for the supported cabling. I. Contractor shall install 3/16-inch polyethylene pulling string in each empty conduit, and appropriately secured at each end. 3.08 COMMUNICATIONS EQUIPMENT ROOMS A. The communications equipment rooms supporting voice, data, and video requirements are identified on the construction documents. B. Prior to the installation of any equipment in any of the communications rooms, the Contractor shall provide room layouts, for University approval, for each of the rooms listed above showing the proposed locations of all backboards, termination blocks, distribution panels, security boxes, control boxes, power supplies, etc. required for all communications systems which are part of this specification. C. Cable must be installed such that station wire runs from the outlet to the cross connect do not exceed 90 meters. D. Grounding shall be #6 AWG wire provided to each communications equipment room in accordance with ANSI/NFPA 780. E. All walls, ceilings and floors must be made non-porous with paint or sealant to minimize dust. F. Sleeves or conduits from outlets shall penetrate closet walls at a height above the plywood panels and extend only far enough to install bushings. G. Hardware shall be installed plumb and level on the wall backboards. Appropriate wire management shall be installed so that jumper, cross connect, and patch cord wires can be installed in a neat and orderly fashion. H. Equipment racks shall be installed level, to manufacturer specifications, and shall be so that jumpers and patch cords can be installed in a neat and orderly fashion. Contractor shall install (1) one equipment rack per (72) seventy-two data outlets. Contractor shall leave the bottom 3 feet of the equipment rack for installation of network infrastructure hardware. Contractor shall appropriately ground all equipment racks in accordance with the National Electric Code (NEC). (April 28, 2000) 3.09 STATION CABLING AND INSTALLATION A. All voice, data, and video outlets shall be installed in the locations that are conspicuously marked in the building floor plans. If there is a question as to the location of any outlet it shall be brought to the attention of the University prior to installation. B. Prior to installing any cabling, drawings indicating all jack numbering shall be submitted by contractor for approval. (April 28, 2000) C. All outlets supporting voice and data communications requirements shall be wired with two (2) 4-pair UTP copper cables (one (1) Lucent Technologies XX61 and one (1) Lucent Technologies XX71 as specified in Part 2.02 of this Section) as well as one (1) unterminated 2-strand multimode optical fiber cable (as specified in Part 2.06 of this Section) The optical fiber cable shall have one meter (1M) slack which shall be coiled in the outlet, and 10 feet of slack neatly coiled in the IDF. For applications where the outlet is designed "DATA ONLY," the outlet shall be wired with one (1) Lucent Technologies XX71 4-pair UTP copper cable and one (1) unterminated 2-strand optical fiber cable. D. Voice or "A" jack: Always the first jack of the outlet designated to accommodate one (1) digital voice station. Wire with one (1) 4-pair Lucent Technologies XX61 UTP copper cable. The "A" jack pairs shall be terminated in the IDF on a 110 block above the voice riser separated by a Lucent Technologies 188 type backboard. E. Data or "B" jack: Always the second jack of an outlet designed to accommodate one (1) digital data station. Wire with one (1) 4-pair Lucent XX71 UTP copper cable and appropriate hardware to classify as a Lucent Technologies Gigaspeed solution. The “B" station cables shall be terminated in the IDF on standard 19" X 84" equipment racks utilizing Gigaspeed rated patch panels and appropriate wire management hardware. F. The terminations in the BDF and all IDFs of all cable pairs for the "A" jacks shall be on termination fields. The Contractor shall not utilize patch cords for “A" jacks. G. All wiring supporting voice and data communications shall conform to IEEE 802.3 10BASE-T wiring standards. H. All voice wiring shall meet Category 5e standards. I. All data wiring shall meet Category 6 standards. 3.10 RISER CABLING AND INSTALLATION A. In the BDF and all IDFs, connecting blocks shall be modular, high-density, Lucent Technologies 110-type or a University approved equal, with clear protective covers. All telecommunication rooms shall be grounded by means of a #6 AWG insulated copper ground wire connected to the building ground system. The BDF shall also have gas element surge protection with sneak fuses adequate for protecting all circuits entering the building. NOTE: All closet layouts shall be approved by the University before installation of any equipment or termination of any wiring. B. Contractor shall install UTP vertical copper cabling between the BDF and each IDF to support voice and data communications requirements. Each riser cable shall be homerun from the BDF to each IDF in the conduit and sleeves provided. In both the BDF and IDF, the cable pairs shall be terminated on Lucent Technologies 110 connecting blocks and appropriately cross-connected to the UTP horizontal copper cabling (in the IDF) and the UTP backbone copper cabling (in the BDF). The size of the riser cables for both voice and data communications from the BDF to each IDF can be found in the Table below. IDF Room Voice Data Number Cable Pairs Cable Pairs C. Riser Multimode Optical Fiber Cabling: For IDFs servicing fewer than seventy-five (75) outlets, twelve (12) tested multimode optical fibers terminated in the BDF fiber patch panels shall be installed to each of those IDFs servicing greater than seventy-five (75) outlets, twenty-four (24) tested multimode optical fibers terminated in the BDF fiber patch panels shall be installed to each of those IDFs and terminated in the IDF. All optical fiber, terminations, and connections shall conform to the IEEE 802.3 10BASE-T specifications. The optical fiber cable provided under this paragraph will support future station "C" jacks. D. Riser Single Mode Optical Fiber Cabling: For all IDF(s) six (6) tested single mode optical fibers terminated in the BDF patch panels separate from multimode optical fiber must be installed. E. Riser Coaxial Cabling: A single RG-11 coaxial cable extending from the BDF to the top floor IDFs shall be installed and used as the riser for each IDF stack. F. "Kellums"- type basket hangers, or a University approved equal, shall be installed on all riser cables to provide independent support of cables passing through conduit sleeves installed in floor slabs. Hangers shall have a maximum separation of twelve (12) inches. 3.11 UNDERGROUND CABLING AND INSTALLATION A. Contractor shall install UTP underground copper cabling between the BDF and the MDF (Main Distribution Frame located in Patuxent Building, Building 010) to support voice and data communications requirements (as specified in Part 2.04 of this Section). The underground cable shall run in the appropriate ductbank and manholes. The contractor shall terminate the underground cable in the cable vault of Building 010 in a Lucent Technologies Cable Rearrangement Facility (vertical splice case). The pairs shall then be run into the frame room of building 010 and terminated on Contractor provided 195A type multi-pair protector panels, and extend tails to 110 field. The Contractor shall also provide new frame racks to support the protector units. The size of the copper underground cable shall be XXXX pairs. The Contractor shall use the largest size of cable applicable. (April 28, 2000) B. Contractor shall install multimode optical fiber backbone cabling between the BDF and the optical fiber hub designated by the University to support data communications requirements (as specified in part 2.06 of this section). The underground multimode optical fiber shall run in innerliner (as specified in Part 2.16 of this Section) in the appropriate ductbank and manholes. The multimode optical fiber shall be terminated on both ends utilizing Contractor provided Lucent Technologies Lightshelves. The size of the backbone multimode optical fiber cable shall be XX strands. C. Contractor shall install single mode optical fiber backbone cabling between the BDF and the MDF to support data communication requirements (as specified in Part 2.06 of this Section). The underground single mode optical fiber shall run in innerliner (as specified in Part 2.16 of this Section) in the appropriate ductbank and manholes. The single mode optical fiber shall be terminated on both ends utilizing Contractor provided Lucent Technologies Lightshelves. The size of the backbone single mode optical fiber cable shall be XX strands. D. Whenever termination points for single and multi mode fiber are the same, a hybrid cable shall be utilized. (April 28, 2000) E. Contractor shall install coaxial backbone cabling between the BDF and the nearest available tap, as designated by the University, to support video communications requirements (as specified in Part 2.12 of this Section). The underground coaxial cable shall run in innerliner (as specified in Part 2.16 of this Section) in the appropriate ductbank and manholes. Cable in the manhole shall be secured to the manhole at least two (2) feet from the connection point and every four (4) feet thereafter. The connector shall be covered with a one (1) foot section of shrink tube except where the connector is located inside the building. Upon completion, the cable now shows no sign of stretches, kinks, or compressions. If damage is apparent, new coaxial cable shall be pulled by the contractor. 3.12 OUTLET BOX INSTALLATION Unless otherwise noted on the drawings, outlets shall be securely and neatly installed at the height specified in the following table: Standard Telephone Outlets: 1ft 6 inches Above Finished Floor (AFF) Wall Mounted Telephone Outlets: 4ft 6inches AFF Wall Mounted for Head On Wheelchair Access: 4ft 0 inches AFF Service Counter Areas: 0ft 8 inches above counter work surface 3.13 DUCTBANK DESIGN, CONSTRUCTION, AND UTILIZATION A. Contractor shall install XXXX pairs (specified and approved by the University) of multipair, UTP copper cable between the BDF and the Patuxent Building (Building 010). Prior to the termination of this cable in the Patuxent Building, Contractor shall verify its termination location with the University. B. Contractor shall install a XXX strand (specified and approved by the University) multimode optical fiber cable (as specified in Part 2.04 of this Section) between the BDF and the multimode fiber optic hub specified by the University. Prior to termination of this cable in the specified location, Contractor shall verify its termination location with the University. C. Contractor shall install a XX strand (specified and approved by the University) single mode optical fiber cable (as specified in Part 2.04 of this Section), between the BDF and the MDF located in the Patuxent Building. Prior to termination of this cable in the Patuxent Building, Contractor shall verify its termination location with the University. D. Contractor shall install one (1) coaxial cable (as specified in Part 2.07B of this Section) between the BDF and the nearest available tap. Prior to termination of this cable Contractor shall verify its termination location with the University. E. Contractor shall install new concrete encased ductbank and manholes and/or install new concrete encased ductbank between existing manholes to accommodate the outside plant needs of the facility as directed by the University. The contractor shall submit proposed pathway for University approval. F. Optical fiber and coaxial cable in the specified amounts above shall be run in one and one quarter (1 1/4) inch innerducts, and copper cable shall be run in 1-1/2" innerducts. Two (2) one and one-quarter (1 1/4) inch and one (1) one and one-half (1 1/2) inch innerducts shall be installed in at least one (1) duct of each ductbank. Ductbank shall be engineered to accommodate the required twisted pair, fiber optic, and coaxial cable needs plus one hundred percent (100%) spare capacity. G. All ductbank shall conform to the provisions and shall be arranged in a rectangular fashion. Only four (4) inch PVC "type B" conduit shall be used for communication ducts. No section of ductbank shall have more than a sum of 180 degrees of bends without the installation of a manhole. (April 28, 2000) H. Ductbanks shall have a minimum of thirty (30) inches cover over encasement. There shall be twenty-four (24) inch minimum clearance between communications ductbank encasement and any other utilities. Note: NO EXCEPTIONS WILL BE MADE WITHOUT PRIOR APPROVAL OF THE UNIVERSITY I. Concrete encased, galvanized intermediate weight rigid steel conduit shall be used instead of PVC or polypropylene wherever ductbanks cross roads, parking lots, or buried steam lines. Steel ducts shall extend ten (10) feet on either side of the crossing. At steam line crossings, encasement shall be covered with an aluminum reflector. J. All spare ducts or those with less than twenty-five percent (25%) fill shall have a one-quarter (1/4) inch polypropylene pull wire appropriately secured at each end. All vacant innerducts or those with less than twenty-five percent (25%) fill shall have a 3/16- inch polypropylene pull wire appropriately secured at each end. K. All ducts shall be pneumatically rodded using a University approved slug of one-quarter (1/4) inch diameter less than the duct inner diameter. L. All ducts, including spares, shall be sealed watertight with an expandable urethane foam at both ends. 3.14 MANHOLES A. Manholes shall have inside dimensions 6 feet Wide x 12 feet 1 inch Deep x 7 feet High (6'-0"W x 12'-1"D x 7'0"H) minimum. B. Manholes shall conform to the provisions. All steel equipment shall be hot dipped galvanized. All manholes shall have at least one (l) 7/8-inch diameter steel pulling eye in the wall opposite each duct entrance. Pulling eyes shall be welded to the reinforcing rods at the time of manhole fabrication. Each manhole shall be equipped with at minimum four (4) cable racks, two (2) per long side, that have adjustable hooks adequately sized to support the hardware. Manhole covers shall have the designation "COMM" cast on the cover. (April 28, 2000) C. New ductbank shall be appropriately doweled to existing manholes. 3.15 CONNECTION TO EXISTING SYSTEM A. Splicing shall only be allowed in manholes or at building entrance locations. No splices shall be allowed in any other location in the new facility or in any ducts or innerliner. Splice cases in manholes shall be securely supported by support hooks on the cable racks not more than two (2) feet away from the splice case. Before closure, all splices shall be offered for inspection by the University and certification of workmanship by Lucent Technologies. B. Contractor shall make all cross-connections in each IDF to connect the first three pairs of each voice UTP horizontal copper cable to the facility copper riser system. C. Contractor shall connect to University video network at the University's direction. 3.16 RE-ROUTING OF EXISTING UNDERGROUND CABLES A. Contractor shall re-route any voice, data, and video cables that are currently located in the space where the new facility is to be constructed to new or existing manholes. The re-routing and manhole locations are conspicuously identified on the site plan of the drawings. B. Contractor shall notify the University at least two (2) weeks in advance prior to any outage, re-routing any existing voice, data, and video cables; and the outage shall be scheduled at the convenience of the University. C. Any cable that is re-routed must be re-terminated and tested according to the termination and testing requirements as described in Part 3.19 of this Section. 3.17 VIDEO SYSTEM INSTALLATION - BUILDING INTERIOR A. The contractor shall provide video system design with loss calculation for University approval before the beginning of installation of any video system cable or equipment. B. Line extenders shall be mounted horizontally five (5) feet above finished floor using two (2) GB13b D-rings secured with eight (8) 1-3/16" screws. At least one (1) line extender must be provided for each IDF stack. Appropriate pads and equalizers shall be installed in the forward line extender section. Return line extenders pads and equalizers may be omitted. C. The first line extender in each IDF stack shall be located in the first floor IDF's. Depending on sign level requirements and the size of the building, additional line extenders in the higher floor IDFs may be required. D. All active and/ or passive devices in an individual BDF or IDF shall be attached together using chassis to chassis or right angle connectors. E. Multiport taps shall be mounted vertically to one (1) GB13a D-ring, with a hex bolt (1/4" wide x 3/4" long) and secured to plywood with four (4) 1-3/16" screws. This does not apply to multiports attached to line extenders. F. The multiport tap, excluding those attached to line extenders shall face either left or right, but not outward into the BDF/ IDF. All unused ports shall be terminated. G. An FFT8-29 multiport shall be the first device attached to the output side of the line extender and is to be used to read the signal levels and measure forward tilt. F-Type right angle connectors may be used for multiport wiring. H. Directional couplers and splitters shall only be used to connect the first amplifiers in the BDF/IDF stacks. I. All IDF/BDFs shall have at least one (l) multiport tap connected to the riser regardless if that IDF/BDF, services any outlets. At every IDF/BDF, a minimum of three (3) spare ports is required. J. In each IDF, the RG-11 coaxial station cable shall be secured to the existing plywood every two (2) feet with screw- type cable tie connectors. Station cable ends in the IDF/BDF shall clearly indicate the outlet and room number of the station end in indelible ink written on plastic cable tags. K. Connectors shall be chosen and installed so they can withstand thirty (30) pounds of pulling force without separating from the cable. 3.18 VIDEO SYSTEM ADJUSTING A. Contractor shall adjust amplifier gain and make other system adjustments to achieve specified output levels at each outlet. 3.19 CABLE PLANT LABELING A. All labeling shall be clear, securely affixed, and consistent on both ends of each installed cable. All labeling shall be approved in advance by the University. B. The labeling of outlets and IDF hardware shall be permanently engraved in the field by the Contractor according to the following numbering system: 1. Each outlet identification code shall consist of five (5) characters. 2. The first character shall indicate the floor of the building where the communications room serving the outlet is located. The number 0 (zero) shall be used for the ground floor, 1 (one) for the first floor, etc. The--letter B shall be used for basements, S for sub- basements, and M, N, and P for mezzanines. 3. The second character shall be used for the communications room identifier. The letters A through Z (except I and O) shall be used and the University will specify the character to be used for each communications room. 4. The last three (3, characters shall denote the number of the outlet. Outlet numbers 1 through 9 shall be preceded with (2) zeros (e.g 004). Outlet numbers 10 through 99 shall be preceded with one (1) zero (e.g. 054). 5. Example: An outlet labeled 1A006 means first floor, IDF "A", outlet number 006. C. The five (5) character code for each outlet shall be permanently marked on the outlet, as well as on the corresponding IDF blocks An outlet with an "A" and "B" jack will have it's identification code appear on both cables at the outlet, as well as in the IDF on both the voice termination field and the data termination field. In addition, each outlet shall be labeled in advance on all telecommunications drawings. D. All unterminated optical fiber horizontal cabling shall be labeled at each end with the outlet number. E. All coaxial cable shall be labeled with an outlet number consistent with the closest voice/data communications outlet. F. All UTP copper riser and underground cable termination blocks shall be labeled with white 110 label strips and shall indicate pair count and destination closet. Voice and data riser shall be labeled separately. G. Underground cable protector units shall be labeled with green 110 label strips reflecting cable pair count and cable number. Underground cable in manholes shall be labeled with engraved brass tag showing cable number where entering and exiting manhole. H. All optical fiber riser and underground cable termination panels shall be labeled with fiber strand count, destination closet, and either “SMOF," “MMOF," or “HYB" to indicate cable type. The underground frame shall be labeled with the fiber strand count, fiber number, and fiber optic hub building number. Underground cable in manholes shall be labeled with engraved brass tag showing cable number where entering and exiting manhole. I. All underground coaxial cable shall be labeled on each end with brass tag marked with the building number and designated as a coaxial feed cable. 3.20 TESTING AND ACCEPTANCE A. Prior to acceptance, all "As-Built" and technical documentation shall be received and approved by the University. As-built documentation shall include the completed and notarized original copy of the Lucent Technologies Systimax Structured Cabling System System Registration Document. All intrabuilding and interbuilding wiring and equipment, and all site restoration shall be installed and completed in accordance with University and industry standards. All wiring and equipment provided and/or installed under this Contract shall be tested as described under the terms of this Contract and shall be fully operational. After all work is complete, the Contractor shall also provide the University with Lucent Technologies Systimax Certification for all communications work completed on the project and Lucent Technologies Distribution Technologies certification for all outside plant splices. B. All copper cable plant testing shall diagnose, at a minimum, the presence of all open-loop conductors, noisy lines and distortion, low-loop current, high-loop current, ringer failures, grounded, shorted or crossed conductors, dB loss, and split connections. Contractor shall perform a continuity test on all pairs installed in the cable plant, both inside and outside the new facility. The testing shall cover end-to-end, from the outlet to the IDF and the BDF to the Patuxent Building (Building 010). In addition, all tests described above shall be performed on a randomly selected pair per twenty-five (25) pair binder group of the copper riser cable. If this random selection is bad, additional testing shall be done to ensure that ninety-nine percent (99%) good pairs exist. The Contractor shall supply complete testing and correction reports to the university for review prior to acceptance of the system. For copper pairs used for the "B" outlet, the Contractor shall perform such additional testing as required to verify that pairs meet the transmission parameters required for 10BASE-T and Category 5 wiring specifications. The University shall have final approval on the format used for recording and reporting of test results prior to the start of testing activities. C. Optical fiber cable testing shall, at a minimum, quantify the attenuation range, optical loss, bandwidth, and misalignment. The cable completion tests shall be performed after all optical fiber cable has been placed and all splicing completed. The contractor shall terminate ten percent (10%) of all installed station fibers for testing purposes. The university will designate which fibers shall be terminated after all cables and wires have been pulled into place. All optical fibers shall be tested at both 850nm and 1300nm. For outside plant fiber, testing shall include two-way testing using an Optical Time Domain Reflector (OTDR), and one-way testing using a Multimode Optical Loss Test Set (MOLTS). For optical fiber installation between the BDF and an IDF, the contractor shall provide two-way loss testing through the use of MOLTS. Two-way MOLTS testing shall also be performed on station fiber terminated for testing purposes. All traces and results shall be provided to the University for approval. Protective covers shall be in place on all connectors when they are not in use to protest against contamination by dirt or dust. Any fiber found to be defective a result of installation, physical inspection, or operational test shall be replaced at the Contractor's expense. D. Coaxial cable and video signal testing shall be performed in the following manner to verify correct installation of coaxial cable and video system electronics: Input Signal @ 450 MHz Output Output@ch.7 (after pad & equalizer) @450 MHz (175.2 MHz) 9 dbmv (+ 1 dbmv) 43 dbmv 40 dbmv FFT8s Located in IDFs: 15 dbmv at 450 MHz at the output of all eight (8) ports of all FFT8s located in the building. 3.21 AS-BUILT DOCUMENTATION A. The contractor shall provide the following outside plant wiring information, prior to acceptance of the building by the University, for each of the specified media: 1. Cable identification number (Copper, Fiber, Coax). 2. Cable design makeup (Copper, Fiber, Coax). 3. Cable lengths between splice points, terminations amplifiers, or line extenders (Copper, Fiber, Coax) 4. Exact routing of cable (Copper, Fiber Coax). 5. Splice location and identification (Copper, Fiber, Coax). 6. Strand count, mode of installed fiber, loss per splice in dB, and total amount of optical fibers installed (Fiber). 7. Frequency rating, location and identification of amplifiers and splitters (Coax). 8. Bonding and grounding (Copper, Fiber, Coax). 9. Location and description of all associated equipment (Copper, Fiber, Coax). 10. Location and description of all associated structures and obstructions. (Copper, Fiber, and Coax). 11. Signal level readings at all line extenders, FFT8s, and all video jacks using frequencies 175.2 MHz (CH. 7) and 450 MHz. B. The Contractor shall provide the following intrabuilding wiring information for each specified media prior to acceptance of the building by the University: 1. Cable entrance locations and penetration details (Copper, Fiber, Coax). 2. Location and identification of all distribution closets and of all equipment located inside distribution closets (Copper, Fiber, Coax). 3. Terminal information, outlet numbering, and pair count information at each distribution frame (Copper). 4. Schematic drawings of riser (Copper, Fiber, Coax). 5. Routing of cable and termination information (Copper, Fiber, Coax). C. The Contractor shall provide the following MDF wiring information prior to acceptance of the building by the University: 1. Cable pair assignments per connector block. 2. Identification of cable routing to MDF. D. The Contractor shall provide a complete listing of pair assignment records for copper wiring, optical fiber cabling, and coaxial cabling. Copper cable records shall include the status of each copper pair. Optical fiber cable records shall include strand allocation, test results, and identification of media and protocol used. E. The Contractor shall provide the University with the operational and maintenance documentation of all telecommunications equipment installed under this contract. F. As-Built drawings shall include actual locations of installed ductbank and manholes, including elevations, and shall indicate location, elevation and type of service for all utilities crossed by the new ductbank. G. Contractor shall submit all drawings on 3.5-inch floppy diskettes utilizing AutoCAD (Latest Version). + + END OF SECTION + +

16.12 Uninteruptible Power System (UPS)


PART 1 - GENERAL

1.01 SECTION INCLUDES

     A.   Uninterruptible power system (UPS).

1.02 SYSTEM DESCRIPTION

     A.   Components:  The UPS shall consist of the following major
          equipment.

          1.   Rectifier/Charger, Invertor, input and output
               transformers, static bypass switch, input and
               output circuit breakers located in a single cabinet
               or group of cabinets.

          2.   External maintenance bypass circuit breakers.

          3.   Battery and battery cabinet.

     B.   Modes of Operation:  The UPS shall be designed to operate
          as an on-line, fully automatic reverse transfer system in
          the following modes.

          1.   Normal:  The rectifier/battery charger shall derive
               power from the commercial AC source and supply DC
               power to the invertor while simultaneously float
               charging the battery.  The critical load shall be
               continuously supplied by the invertor.

          2.   Emergency:  Upon failure of the commercial AC
               power, the critical load shall continue to be
               supplied by the invertor which without any
               switching, obtains its power from the storage
               battery.  There shall be no interruption of power
               to the critical load upon failure or restoration of
               the commercial AC source.

          3.   Recharge:  Upon restoration of the commercial AC
               source, the rectifier/charger shall power the
               invertor and simultaneously recharge the battery. 
               This shall be an automatic function and shall cause
               no interruption of power to the load.


          4.   Bypass Mode:  If the UPS must be taken out of
               service for overload or internal failures, the
               static bypass switch shall automatically transfer
               the load without interruption, to the commercial AC
               power.  Retransfer of the load to the normal mode
               shall be automatic after the overload or failure
               has been cleared and reset.  Transfer to bypass
               shall also be initiated manually for maintenance or
               repair.

          5.   Downgrade:  If the battery needs to be taken out of
               service for maintenance, the battery shall be
               disconnected from the UPS module by means of an
               internal battery circuit breaker.  The UPS shall
               continue to function and meet all performance
               criteria specified herein, except for the reserve
               time capability.

     C.   Design Requirements:  The UPS system shall be field-
          upgradable to 50 KVA.

1.03 APPLICABLE STANDARDS

     A.   The UPS shall meet the requirements of the following
          standards (latest edition):

          1.   ANSI C84.1 - Voltage ratings for Electric Power
               Systems and equipment.

          2.   ANSI/NEMA 250 - Enclosures for Electrical Equipment
               (1000 volts maximum).

          3.   NEMA PE1 - Uninterruptible power systems.

          4.   ANSI C 62.41/IEEE 587 - standards for surge with
               standability.

          5.   FCC Part 15, Subpart J, Class A.

          6.   NFPA 70 - National Electrical Code.

     B.   The UPS shall be UL listed under UL 1012.

1.04 SUBMITTALS

     A.   Shop Drawings:  Submit system configurations with single
          line diagrams, detailed layouts of power and control
          connections, ladder diagrams for the maintenance bypass
          scheme, and detailed installation drawings including all
          terminal locations.

     B.   Product Data:  Provide product data for UPS and battery
          including catalog sheets and technical data sheets to
          indicate electrical performance, UPS type, battery type,
          detailed equipment outlines, weight, dimensions, control
          and external wiring requirements, heat rejection and air
          flow requirements.

     C.   Submit manufacturer's installation instructions under
          provisions of Division 1.

     D.   Submit manufacturer's certificate showing that the system
          meets or exceeds the specified requirements.

     E.   Submit a copy of factory test reports to the University,
          before shipment of the equipment.

1.05 ENVIRONMENT CONDITIONS

     The UPS shall be able to withstand the following environmental
     conditions without damage, derating or degradation of
     operating characteristics:

     A.   Operating Ambient Temperature

          UPS: +10øC to +40øC
          Battery: +10øC to +40øC

     B.   Storage/Transport Ambient Temperatures

          UPS: -20øC to +60øC
          Battery: -20øC to +60øC

     C.   Relative Humidity (operating and storage) 0 to 95%, non-
          condensing.

     D.   Elevation:  5,000 feet

     E.   Acoustical noise:  65 dBA to one meter from any operator
          surface, measured at full load on invertor, at 25øC.

1.06 QUALITY ASSURANCE

     A.   Manufacturer Qualifications:  Company specializing in UPS
          equipment with a minimum of three years experience in the
          design, manufacture, and testing of solid-state UPS
          systems.

     B.   Factory Testing:  The manufacturer shall fully and
          completely test the system to assure compliance with the
          specifications, before shipment.

1.07 WARRANTY

     The manufacturer shall warrant the complete Uninterruptible
     Power System against defective material and workmanship for a
     period of five (5) years and shall provide a minimum of two
     (2) preventative maintenance service calls per year by
     qualified factory service technicians during this period. 
     This warranty period shall commence with the date that the
     University takes over the building.


PART 2 - PRODUCTS

2.01 SYSTEM REQUIREMENTS

     A.   System Efficiency:  The overall system AC to AC
          efficiency shall be determined by dividing the output
          power by the input power.  The battery shall be fully
          charged and connected.  The rectifier/battery charger
          shall be in the normal float mode.  The invertor shall be
          operating in the normal mode.

          The minimum acceptable efficiency values are 83% at 50%
          rated load, 84% at 75% rated load, 86% at 100% rated
          load.

     B.   Components:  All active electronic devices shall be
          solid-state and shall not exceed manufacturer recommended
          tolerances for maximum reliability.  All semiconductor
          devices shall be sealed.  Vacuum tubes shall not be used. 
          All relays shall be provided with dust covers.

     C.   Grounding:  The UPS output AC neutral shall be
          electrically isolated from the UPS chassis, battery, and
          main ac input.

     D.   Conductors:  All wiring, including transformers and
          inductors, and all other conductive components shall be
          copper for maximum safety and reliability.  All exposed
          copper surfaces shall be treated with a suitable
          permanent protective coating electrically equivalent to
          tin.  Aluminum wiring, foil or bus work shall not be
          used.  Aluminum shall not be used as a current carrying
          media.  Aluminum heat sinks may be used provided that no
          electrical current passes through the part.

     E.   Power Transformers:  Input and output power transformers
          shall be designed and manufactured for maximum safety,
          reliability, and efficiency.  All input and output
          transformers shall be of the isolated winding type.  All
          windings shall be copper.  Input transformer(s) shall
          have an electrostatic shield between primary and
          secondary windings for noise isolation and suppression. 
          Insulation type shall have a temperature rating that is
          greater than the highest winding temperature during worst
          case UPS operation.  All transformer connections shall be
          accessible from the front of the enclosure to facilitate
          periodic inspection and maintenance.

     F.   Materials:  All materials and parts comprising the UPS
          shall be new, of current manufacture, and shall not have
          been in prior service, except as required during factory
          testing.  All metal surfaces shall be treated with a
          corrosion inhibiting permanent protective coating.

     G.   Sag/Surge/Impulse Protection:  The UPS shall have built-
          in protection against sag/surge/impulse disturbances on
          both the main and bypass ac input sources.  These
          disturbances shall include, but not limited to, the
          effects of load transfer between the invertor and bypass
          ac source as well as low energy induced transients
          resulting from the proper operation of correctly applied
          lightning protection systems.

     H.   Reliability:  The UPS Module shall have an internal Mean
          Time Between Failure (MTBF) of not less than 50,000
          hours.  This requirement shall be based upon actual field
          experience using representative data from all installed
          UPS models of the specified series and/or rating.  For
          the purpose of determining  specified reliability, the
          bypass AC input source shall not be used as an
          enhancement method.

     I.   Overtemperature Protection:  The rectifier/charger heat
          sink and the invertor heat sinks shall be protected by
          temperature sensors so that the UPS will shut down before
          any semiconductor devices are damaged by over
          temperature.  When a sensor is activated, the UPS shall
          transfer the critical load to bypass.

2.02 MANUFACTURER

     The UPS system shall be as manufactured by Exide Electronics,
     Powerware System 50, Model 20 or approved equal.

2.03 ELECTRICAL CHARACTERISTICS

     The UPS shall have the following electrical characteristics:

     A.   Input

          1.   Input voltage:  480 volts, 3 phase, 4 wire.

          2.   Voltage range:  +10%, -20% without battery
               discharge.

          3.   Frequency:  60 Hertz, ñ 5%.

          4.   Input power factors:  0.95 lag minimum.

          5.   Input current total harmonic distortion (THD): 10%
               maximum.

     B.   Output

          1.   Nominal output voltage 208/120 volts, 3 phase, 4
               wire plus ground.

          2.   Frequency:  60 hertz ñ 0.1%

          3.   Rating:  20 KVA, 16 KW at 0.8 p.f lagging.


2.04 COMPONENTS

     A.   Rectifier/Charger:  Incoming AC power shall be converted
          to regulated DC by the rectifier/charger.  The
          rectifier/charger shall be a phase controlled, solid-
          state type with constant voltage and constant current
          control circuitry.  The rectifier shall be provided with
          a timed walk-in circuit, with loading over a period of 15
          seconds.

     B.   Invertor:  The invertor shall be transistorized, pulse-
          width-modulation design.

     C.   Static Transfer Switch and Bypass:  The static transfer
          switch and bypass shall be provided as an integral part
          of the UPS.  The control unit shall include transfer
          circuitry that senses the status of the invertor logic
          signals and alarm conditions to provide an uninterrupted
          transfer of the load to bypass.  Return to normal mode of
          operation shall be automatic, upon restoration of normal
          operating conditions, except for invertor failure or
          overload.

     D.   Input and Bypass Protection:  Thermal-magnetic molded
          case breakers and transient suppression circuitry shall
          be provided for input and bypass protection.

     E.   Battery and Battery Cabinet:  The stationary storage
          battery system shall be sized to meet or exceed the 100%
          UPS output requirement for a minimum of ten (10) minutes. 
          The individual battery shall be sealed, maintenance free,
          non-gassing absorbed electrolyte type with automatic/self
          sealing safety vents, heavy duty integral copper
          terminals, heavy duty lead plated copper connectors, and
          stainless steel bolts and lockwashers.  The battery shall
          be housed in a separate cabinet(s) to match UPS cabinets,
          with casters and leveling feet.  Battery shall have
          minimum 10 years expected life covered by warranty
          through the manufacturer.  Battery short circuit
          protection shall be provided by a molded case circuit
          breaker located in the battery cabinet.

     F.   Control and Monitoring Panel:  The UPS shall be equipped
          with control and monitoring panel that provides metering,
          monitoring, and control functions.  An Emergency Power
          Off (EPO) pushbutton shall be located on the control and
          monitoring panel.

     G.   Remote Monitor Panel:  A remote monitor panel shall be
          provided and shall be connected to the UPS via the RMP
          interface.  A panel shall have a local audible alarm horn
          and three user selectable alarm indicators.

     H.   Input Filter:  An input filter with power factor
          correction shall be provided in a matching cabinet.

     I.   External Maintenance Bypass Circuit Breakers and
          Enclosure:
          A separate maintenance bypass shall be provided to allow
          complete isolation of the load from the UPS.  The bypass
          scheme shall consist of two non-automatic, molded case
          circuit breakers provided in a separate NEMA 1 enclosure. 
          The operation of the external bypass breakers shall be
          enabled only when the UPS is in bypass mode.  The closing
          of the invertor output contractor or breaker shall be
          inhibited during the transfer or retransfer operation. 
          Kirk Key interlocks with two sets of keys shall be
          provided such that only one breaker can be in the open
          position at all times and power supply to the load is
          never interrupted.

     J.   Remote Alarm Panel:  A remote alarm panel shall be
          provided, and shall be connected to the UPS.  A summary
          alarm dry contact shall be provided on the UPS for
          indicating any alarm condition at the new alarm panel to
          be located in the telecommunication switch room in the
          existing building.  The sequence of operations in the
          alarm panel shall be as follows:  One green indicating
          light shall display the systems normal; the alarm
          condition shall flash the red indicating light and sound
          the local alarm horn; the acknowledge pushbutton shall
          stop the horn and the light shall be steady on until the
          panel is reset; the reset button shall return the panel
          to normal only after the alarm condition on the UPS has
          been cleared.
     
PART 3 - EXECUTION

3.01 INSTALLATION

     A.   The UPS system shall be installed in the UPS room. The
          remote monitor panel and the remote alarm panel shall be
          provided as per University requirement.

3.02 TESTING

     A.   Before application of primary power, all connections
          shall be verified for correct phase rotation.

     B.   The Contractor shall provide all equipment necessary for
          load testing including a load bank equivalent to the full
          capacity of the UPS.  Any additional ventilation required
          shall be provided by the contractor.

          1.   Pre-Start-Up Tests:  All manufacturer required or
               suggested "Prestart-up Tests" shall be performed.

          2.   Primary Power Application:  Primary power shall be
               applied only after the successful completion of the
               "Pre-start-up Tests".  Primary power shall be
               applied for a minimum of seventy-two (72) hours
               with the dummy load operating, prior to the
               initiation of additional required tests.  During
               this period of operation, all functions of the UPS
               shall be continuously monitored.  The load testing
               of the system with load bank shall be conducted
               only once.  Run down time and battery back-up shall
               be monitored and verified as well as the recharge
               time of the batteries as specified or as listed by
               manufacturer as minimum.

          3.   Operational Tests:  After the initial seventy-two
               (72) hours of operation, the Contractor, under the
               direction of a skilled and qualified technical
               representative of the manufacturer, shall non-
               harmfully induce conditions necessary to
               successfully test and assure the proper operation
               of all alarms, overrides, transfers and/or
               bypasses.

          4.   Final Acceptance Test:  The UPS shall have been in
               service for at least thirty (30) days prior to the
               final inspection.  The Contractor shall notify the
               Construction Manager in writing within five (5)
               working days prior to the date of the final
               acceptance tests.  The UPS shall be considered
               ready for such testing only after all necessary
               preliminary tests have been made and all defects
               and deficiencies found have been corrected to the
               satisfaction of the equipment manufacturer's
               technical representative.  The UPS shall be
               acceptance tested in the presence of
               representatives of the manufacturer, the
               Construction Manager, the University of Maryland,
               College Park. The Contractor shall furnish all
               instruments, labor and materials required for the
               tests; and the technician who supervised the
               installation shall conduct the tests.  Any
               deficiencies found shall be corrected and the UPS
               retested at no cost to the University.  All tests
               shall be repeated as directed by the Construction
               Manager during final acceptance testing period to
               his satisfaction at no additional cost.

          5.   Additional Tests:  When deficiencies, defects
               normal functions develop during required testing,
               all further testing of the UPS shall be suspended
               until proper adjustments, repairs, corrections or
               revisions have been made to assure proper
               performance of the system.  If these adjustments,
               repairs, corrections or revisions require more than
               a nominal delay, the observers as herein before
               indicated shall be notified when the additional
               work has been completed to arrange a time for a new
               final inspection and test of the equipment
               involved.  All tests required shall be repeated
               prior to final acceptance, unless directed
               otherwise.

          6.   Maintenance Instructions:  Submit to the
               Construction Manager with the initial notification
               of final acceptance testing, a complete set of
               reproducible as-built, approved wiring and
               interconnection wiring diagrams with four (4) sets
               of copies, and four (4) complete sets of
               maintenance manuals.  This is in addition to the
               requirements of Division 1.

          7.   Instruction of Owner's Personnel:  Upon completion
               of the work and at a time designated by the
               Construction Manager, designated personnel at the
               activity shall receive a complete training session
               of 20 hours, comparable to the equipment
               manufacturer's factory training procedure.  The
               training shall include an explanation and review of
               the theory of operation, the function, description,
               analysis, and the trouble-shooting of all equipment
               provided.  Training shall include a review of
               manuals, drawings, and lists supplied, together
               with any clarifications required.  At least one
               period of eight hours shall be spent demonstrating
               routine maintenance procedures and trouble-shooting
               equipment with actual faults being introduced for
               training purposes.   The instruction personnel
               shall be factory certified by the related equipment
               manufacturer to provide instruction services.  The
               training shall take placed at the site.

16.13 Utility Metering


     A.   All utilities serving a building shall be metered.

     B.   Temporary utility meters are required during construction
          and shall be included in the specifications.

     C.   Water, electric, and steam utilities shall be remotely
          metered.

     D.   Water meters shall incorporate flange meters at all
          locations.  For 2" meters or smaller, rotating disk type
          shall be used.  For 2 «" or greater, turbine type shall
          be used.  Pulse weighing shall be not less than 1
          closure/100 gallon on 2" or smaller and 1 closure/1000
          gallons on 2 «" or greater.  A Trican "S" head shall
          provide dry contact operation for FM use.

     E.   All sub-metering opportunities will be identified.  When
          sub-metering is appropriate, the specified meter and
          installation shall be inspected and certified by the
          appropriate governing agency.

     F.   Steam utility shall be metered via turbine type
          condensate meters.  Pulse output shall be made available
          via dry contacts for CCMS use.

     G.   Condensate shall exit to a condensate return system.
          Condensate shall not be discharged to sanitary sewer.

     H.   All service conductors entering a building shall be
          metered.  All electrical metering at service entry shall
          utilize campus standard Time of Use electronic
          registration with remote communication via Sangamo's 
          ST-MT100 register (or its current replacement), T3000 meter
          interface unit (or current production model), induction
          disk meter body, and polycarbonate cover with Optocom
          port.

     I.   Where building service provides power to computer systems
          requiring three phase, uninterruptable power supply, the
          electrical load shall have electrical monitoring for 
          on-line alarming and documentation.  The hardware used shall
          conform to existing campus locations and the software
          used to interrogate these installations.

     J.   Service entry locations and critical load distribution
          locations shall be served by a standard telephone
          service.  This service shall be a hard wire bridge to an
          analog service existing in the building.  If an analog
          courtesy phone is applied anywhere in the building a
          bridge shall be provided via a jack at the BDF.  One
          analog bridge will be required per meter interface unit,
          MIU, (T3000).  If no line exists a separate line should
          be provided to serve the MIU.

16.14 Variable Frequency Drive (VFD) Requirements


     A.   Control Frequency Drives shall be manufactured by a
          single contractor utilizing a sine coded pulse width
          modulated invertor control.  The variable speed drive
          units applied to various HVAC systems shall be provided
          with designs utilizing the following basic
          criteria/specifications:

          1.   Converter shall consist of a modular assembly
               consisting of a diode rectifier and capacitor
               assembly which will first convert, then filter and
               maintain a fixed DC voltage source from the fixed
               voltage and frequency input.

          2.   Invertor shall be Insulated Gate Bipolar Transistor
               (IGBT) with a minimum rating of 1000 VDC on 460 VAC
               controls to invert the converter fixed DC voltage
               into a sine-coded pulse with  modulated output.

          3.   Control Logic to consist of a single printed
               circuit board for all horsepower sizes and
               incorporates an 8 bit, or larger, microcomputer
               central processing unit to control all invertor,
               converter, base drive, and external interface
               functions.

     B.   The VFD unit shall allow application onto systems
          whichemploy any NEMA-B induction squirrel cage motor.

     C.   The selected VFDs shall provide user friendly diagnostics
          clearly displayed at a front display.

     D.   The following identifies the minimum features to be
          noted in a design:

          1.   Standard line input voltage 460 VAC.

          2.   Shall not induce voltage line notching into the
               utility line.

          3.   The VFD units shall be controlled automatically a
               4-20 mA control signal.

          4.   The VFD shall be UL approved.

          5.   The VFD shall be designed to meet power line       
               transient conditions defined within IEEE-587.

          6.   The VFD shall comply with 1990 NEC.

          7.   The VFD shall contain the following general
               features:

               a.   Automatic restart after power outage and fault 
                     occurrences of over current or over voltage.

               b.   Control follower circuit board to utilize 4-20 
                     mA control signal.

               c.   Electronic overload protection.

               d.   Hand/Off/Auto operator switch.

               e.   Instantaneous electronic trip when 180% FLA                 
                    sensed, phase to phase output short or phase
                    to ground output short circuit occurs.

               f.   Interface for time clock control.

               g.   Line circuit breaker.

               h.   Manual bypass (door interlocked) for fixed 60 
                     Hz operation in emergency.

               i.   Manual speed potentiometer.

               j.   Minimum/Maximum adjustable speeds.

               k.   Over-temperature protection.

               l.   Panel mounted display of status, frequency,   
                     service diagnostics.

               m.   Run/Stop command switch.

               n.   Shall provide for 100% current limit.

               o.   Thermal overload relay.

               p.   Timed acceleration and deceleration for soft
                    starting and stopping.

16.15 Medium Voltage Electrical Testing


PART 1 - GENERAL

     A.   The inspection and testing of medium voltage components
          shall be performed by an independent testing agency.  The
          inspection and testing shall be applied for, coordinated
          and paid by the construction contractor.

1.01 SCOPE OF WORK

     A.   The testing agency shall furnish all labor, materials,
          equipment, supervision, and insurance necessary to
          provide electrical acceptance testing including load
          surveys, power line disturbance studies, calibration and
          adjustment of relays, PCB sampling, ground resistance
          tests, transformer tap adjustments and testing on high
          voltage apparatus such as cables, switchgear, and
          transformers at the University of Maryland installations
          on demand.

1.02 SUBMITTALS

     The construction contractor shall submit the following to the
     Department of Architecture, Engineering & Construction and get
     approval in writing prior to entering into a contract with the
     testing agency or initiating any testing.

     A.   Documentation supporting the testing agency
          qualifications (per article 4 of this specification).

     B.   The name(s) and certifications of the members of the
          testing teams.

     C.   The name and State of Maryland registration number of the
          registered electrical engineer responsible for testing
          and evaluation of the test data.

     D.   Certificate of the testing firm's insurance containing
          evidence of the "Hold Harmless" clause protecting the
          University of Maryland from all, suits, actions or
          claims.

1.03 QUALIFICATIONS OF TESTING AGENCY

     A.   Requirements

          1.   Testing Agency shall be limited to any firm,
               company, or corporation in the electrical testing
               industry providing the following qualifications are
               met:

               a.   They shall be regularly engaged in the
                    technical testing, maintenance, and repair of
                    electrical materials, devices, appliance,
                    electrical installation, and systems for the
                    purpose of preventing injury to persons or
                    damage to property and other equipment.  This
                    type of business shall constitute the firm's
                    principal source of revenue.  Equipment
                    installation and/or services normally
                    performed by manufacturers, contractors,
                    consulting firms, producers, suppliers,
                    vendors or installer shall constitute less
                    than twenty-five percent (25%) of total
                    revenue.

               b.   The testing firm shall meet federal OSHA
                    criteria for Accreditation of testing
                    laboratories, Title 29, PARTS 1907, 1910, and
                    1936.

               c.   They shall be engaged in such practice for a
                    minimum of two (2) years and must have a
                    minimum of one (1) registered professional
                    electrical engineer, licensed in the State of
                    Maryland who has been regularly engaged in
                    over 600 volt acceptance testing for a periods
                    of not less than five (5) years and shall be
                    responsible for all phases of testing and
                    maintaining electrical power systems including
                    short circuit analysis, protection
                    coordination studies, and the evaluation of
                    test and maintenance data.  The engineer shall
                    review and evaluate all results and issue a
                    certified test report.

                    1.   Any company with fewer than twelve (12)
                         test technicians may meet the
                         professional Engineer requirement by
                         contracting with a State of Maryland
                         registered Professional Engineer for
                         review of all short circuit studies,
                         overcurrent coordination studies, and
                         other engineering reports, who meets the
                         above 4.A.1. criteria.

                    2.   Any company which employs twelve (12) or
                         more test technicians for twelve (12)
                         consecutive months must employ a full
                         time State of Maryland registered
                         Professional Engineer who meets the above
                         4.A.1 criteria.

               d.   The testing firm must have in their employee a
                    minimum of two (2) two-person test teams who
                    are employed full time by the firm for testing
                    services.

                    1.   The members of the testing teams shall be
                         currently certified by the International
                         Electrical Testing Association (NETA) in
                         Electrical Power Distribution System
                         Testing, or certified as an Engineering
                         Technician in Electrical Testing
                         Engineering Technology by the National
                         Institute for Certification in
                         Engineering Technologies (NICET).

               e.   They must agree to perform all work according
                    to the guidelines of the approved testing
                    standards for equipment of their class and
                    type.  However, job specifications shall take
                    precedence over approved testing standards for
                    equipment of their class and type guidelines.

               f.   They shall be corporately and financially
                    independent testing organizations which can
                    function as unbiased testing authorities,
                    professionally independent of the
                    manufacturers, contractors, counseling firms,
                    producers, suppliers, vendors or installer of
                    equipment or systems of a type evaluated by
                    the design organization.  such a testing
                    organization or laboratory is defined as
                    follows:

                    The testing organization or laboratory is
                    legally constituted to perform testing and is
                    independent of manufacturers, contractors,
                    consulting firms, producers, suppliers,
                    vendors and installers.  "Independent" as used
                    herein shall be defined as an organization or
                    laboratory which meets all of the following
                    criteria:

                    1.   Such individual group, organization or
                         laboratory shall be free of common
                         ownership or control of manufacturers,
                         contractors, consulting firms, producers,
                         suppliers, vendors, or installers of
                         equipment.  As used herein, the following
                         terms shall have the following means:

                         a.   To own means to own, control or
                              influence a majority of the voting
                              rights in the testing organization
                              or laboratory.

                         b.   To control means to be able to
                              formulate, determine, or veto basic
                              business policy decisions of the
                              testing organization or laboratory. 
                              It is not necessary for another
                              company to own the testing
                              organization or laboratory to
                              control it; it may exercise control
                              through use of dominant minority
                              voting rights, proxy voting,
                              contractual arrangements or
                              otherwise.

                         c.   A manufacturer means an individual,
                              group or organization whose primary
                              business is to design or assemble,
                              or cause to be assembled, products
                              which would customarily be tested
                              and evaluated for conforming tot he
                              manufacturer's specified performance
                              criteria by a member of the
                              International Electrical Testing
                              Association or distribution of
                              electrical power.

                         d.   A contractor means an individual,
                              group or organization whose primary
                              business is the construction and/or
                              installation of electrical power
                              distribution equipment, systems or
                              facilities.
                         
                         e.   A consulting firm means an
                              individual, group or organization
                              whose primary business is the
                              concept, design, supervision, and/or
                              management of projects that include
                              electrical power distribution
                              equipment, systems or facilities.

                    2.   It has no managerial affiliation with
                         manufacturers, contractors, consulting
                         firms, producers, suppliers, vendors or
                         installers.

                    3.   It  has sufficient breadth of interest or
                         activity so that the loss or award of a
                         specific contract to determine the
                         compliance of a product with the
                         applicable test standard would not be a
                         substantial factor in the financial well-
                         being of the organization or laboratory.

                    4.   The employment security status of the
                         personnel of the organization or
                         laboratory is free of influence or
                         control of manufacturers, suppliers,
                         vendors, and installers.

                    5.   The organization of laboratory is not
                         engaged in the promotion of the product.

               g.   The testing organization or laboratory shall
                    have a minimum of four (4) or twenty-five
                    percent (25%) of their field testing personnel
                    (whichever is greater) approved as NETA
                    Certified Test Technicians or NICET Certified.

1.04 SAFETY AND PRECAUTIONS

     A.   All work shall be performed in accordance with applicable
          regulations of the Occupational Safety and Health
          Administration (OSHA), the Maryland Occupational Safety
          and Health Administration, the National Fire Protection
          Association - NFPA 70E, ANSI-C2 National Electrical
          Safety Code and the American National Standards for
          Personnel Protection.
     
     B.   No work involving reaching into or dismantling of
          equipment, work in the immediate vicinity of exposed
          electrical connections, or work involving the handling of
          hazardous materials shall be performed by any employee of
          the test agency except int he immediate presence of
          another employee of the test agency who is capable of
          rendering assistance in case of an emergency.

     C.   It is the intent of this contract that all test
          procedures shall be provided by a two-person team of the
          testing agency.

1.05 LOCAL CONDITIONS COVERING WORK

     A.   The testing firm shall cooperate with those in authority
          on the premises in bringing, storing, or removal of all
          materials and equipment, to observe all rules and
          regulations in force on the premises, avoid unnecessary
          dust or accumulated debris, or the undue interference
          with the convenience, sanitation or routine of the
          University of Maryland, and to prevent the loss of, or
          damage to the property of the University of Maryland
          and/or its employees.

          The testing firm shall repair any and all damage he/she
          may cause to the building or property, to the full
          satisfaction of the staff of the Department of
          Architecture, Engineering & Construction.

     B.   Special precautions shall be exercised in accordance with
          the regulations of the particular institution when
          testing at some hospital centers.

1.06 RESPONSE TIME

     A.   The testing agency shall respond to routine test requests
          by the Contractor or the University of Maryland within 72
          hours of request.

     B.   Response time for location/identification of equipment
          failures shall be within three (3) hours of receipt of
          request.

1.07 TECHNICAL STANDARDS AND LIBRARY

     A.   The testing procedures to be performed under this
          contract shall be in accordance with the latest
          applicable requirements of ANSI, ASTM, IEEE, ICEA, NFPA,
          OSHA, EPA, NETA, and the Doble Engineering Company.  The
          testing agency shall maintain in-house the latest copies
          of these standards, codes, and recommended practices.

          1.   In particular, copies of standards and codes
               pertaining to the following electrical equipment
               and testing practices must be available in-house
               for ready reference upon demand: 

               a.   Power cables of all types and of all
                    distribution voltage ratings.

               b.   Medium voltage switchgear of all types.

               c.   Medium voltage circuit breakers and switches
                    of all types.

               d.   Dry-type and liquid-filled power and
                    distribution transformers.

               e.   Protective relaying and protection system
                    requirements.

               f.   Current transformer and potential
                    transformers.

               g.   Voltage regulators.

               h.   Surge arresters and capacitors.

               i.   Metering apparatus.

               j.   Motors.

               k.   Generators and Motor Generator sets.

               l.   Grounding systems.

          B.   The testing company must have in its in-house
               technical library the following reference
               electrical manuals of the latest edition:

               *    OSHA CFR 29
               *    IEEE Color Book Series
               *    Electrical Engineering Handbook
               *    applies Protective Relaying Handbook
               *    NETA Acceptance Testing Specifications
               *    Electrician's and Technician's Handbooks
               *    NFPA-70E
               *    ANSI-C2
               *    ANSI-C39

               1.   Furthermore, reference library of various
                    electrical equipment manufacturer's technical
                    pamphlets or manuals for the variety of
                    electrical equipment commonly in use must be
                    maintained in-house.  The manuals and
                    reference technical data must be published by
                    the manufacturers of switchgear, circuit
                    breakers, transformers, protective relays,
                    cables, bus ducts, motors, metering and other
                    power and control equipment being tested
                    regularly.

1.08 UNIVERSITY OF MARYLAND RIGHTS OF INSPECTION AND TEST

     A.   The University of Maryland reserves the right to make or
          cause to be made such inspections and tests as deemed
          advisable to ascertain that the requirements of these
          specifications are being fulfilled.  Should it be found
          that the standards herein specified are not being
          satisfactorily maintained, the University of Maryland
          may, by written notice to the Contractor, terminate this
          testing agency services.  In such event, the University
          of Maryland may take over the work and prosecute it to
          completion, by contract or otherwise, and the contractor
          and his sureties shall be liable to the University of
          Maryland for any additional costs occasioned by the
          University of Maryland.

1.09 TESTING AND INSPECTION PROCEDURES

     A.   Prior to the energization of any new and/or relocated
          high voltage apparatus (above 600 volts) such as cables,
          transformers, and switchgear, the following field
          inspections and tests shall be performed.  It shall be
          the responsibility of the electrical contractor doing the
          construction to advise and coordinate the test procedures
          including cable preparation with the testing agency.

     B.   In Power Company service entrance applications, unless
          otherwise required by the Power Company, it shall be the
          responsibility of other than the testing agency to
          deliver draw-out elements of overcurrent relays to the
          Power Company's Laboratory for inspecting, testing, and
          setting prior to the equipment being placed in service.

     C.   The scope of inspection and testing services for medium
          voltage electrical equipment includes but is not limited
          to the following:

          1.   Switchgear and switchboard assemblies

          2.   Transformers
               a.   Dry-Type
               b.   Liquid Filled
               c.   Small Dry-Type

          3.   Cables - Medium Voltage

          4.   Metal Enclosed Bus

          5.   Air Switches
               a.   Medium Voltage - Metal Enclosed
               b.   Medium voltage - Open

          6.   Circuit Breakers - Medium Voltage
               a.   Air Filled
               b.   Oil Filled
               c.   Vacuum

          7.   Protective Relays

          8.   Instrument Transformer

          9.   Metering and Instrumentation

          10.  Grounding System

          11.  Motor Control - Medium Voltage

          12.  Surge Arresters - Medium Voltage

          13.  Capacitors

          14.  Automatic Circuit Reclosers - Medium Voltage - Oil
               and Vacuum

          15.  Automatic Line Sectionalizers - Medium Voltage -
               Oil

     D.   The testing scope and procedures for those items noted in
          paragraph 10C above shall be in accordance with Section
          7 of the latest edition of NETA Acceptance Testing
          Specifications for electrical Power Distribution
          Equipment and Systems.  Optional test procedures noted in
          Section 7 are not required to be accomplished except as
          follows:

          1.   Section 7.3.2.2. - Cable insulation resistance
               testing utilizing a megohm-meter shall be provided.

          2.   Section 7 of the latest NETA Acceptance Testing
               specifications for Electrical Power Distribution
               Equipment and Systems is made inclusive of this
               contract by reference.

1.10 TEST EQUIPMENT AND TEST EQUIPMENT CALIBRATION

     A.   All test equipment required to price the services
          outlined in this specification shall be in the testing
          agency's inventory or shall be procured by the testing
          agency, if required, at no additional cost to the
          University of Maryland.

     B.   The testing firm shall have a calibration program which
          assure that all applicable test instruments are
          maintained within rated accuracy.

          1.   The accuracy shall be directly traceable to the
               National Institute of Standards and Technology.

1.11 PCB ANALYSIS UNIT PRICES

     A.   Upon request by staff engineers of the Department of
          Architecture, Engineering & Construction, the testing
          firm shall obtain the following suspected PCB
          contaminates, analyze same for degree of contamination,
          and report the results.  these services shall be billed
          at the contractual hourly rate for labor plus the
          contractual unit price for the PCB laboratory analysis
          noted in the Bid Form.  All testing shall be in
          accordance with EPA prescribed methods.

          1.   Provide unit price for laboratory analysis for PCB
               contamination of a suspected oil sample.

          2.   Provide a unit price for a wipe sample of suspected
               contaminated surfaces.

          3.   Provide a unit price for concrete core samples. 
               Core samples shall be one (1) inch diameter by
               three (3) inches deep.

               a.   The samples shall be obtained with a diamond
                    bit and water coolant system.  The core
                    samples shall be pulverized and dried for a 24
                    hour period.  The PCB shall then be extracted
                    from each sample for a period of two (2) hours
                    using EPA recommended techniques.  The
                    analysis is completed by injection into a gas
                    chromatographic system with subsequent
                    computation and report in PPM.

               b.   Though there are no present EPA specifications
                    or standards for this criteria, laboratory
                    analysis shows a 1:2 extraction ratio for this
                    process.

               c.   The holes shall be patched with Super Por-Rok,
                    or approved equal, non- shrink grout.

1.12 DEMAND VISITS

     A.   In addition to the acceptance testing of medium voltage
          electrical equipment the testing agency shall also
          provide fault identification services for cable,
          transformer, switchgear, etc., failures on demand. 
          Additional services such as load surveys and device
          testing for over and under 600 volt applications may be
          required.

1.13 TEST RESULTS

     A.   All test data shall be recorded on standard National
          electrical Testing Association (NETA) forms or forms
          developed by a manufacturer for use with specific test
          equipment and approved by the University of Maryland.

     B.   All test results shall be typewritten when submitted in
          their final forms and shall include the assigned
          University of Maryland project number, job name and
          location.
     
     C.   Under "Remarks" Column, an analysis of the test data
          shall be given indicating whether data recorded is or is
          not within accepted limits.

     D.   Normally five (5) copies of final report shall be
          submitted with copies going to each of the following:

          1.   Department of Architecture, Engineering &
               Construction Project Manager (2 copies).

          2.   Consulting Engineer responsible for the particular
               project (1 copy).
          
          3.   In Power Company service entrance application, all
               test results and applicable field inspection
               reports shall be forwarded to the applicable Power
               Company (1 copy).

               Test result reports shall be submitted with copies
               as noted within five (5) working days of the date
               of the test.

               Immediately upon the completion of the testing of
               each high voltage system component (cables,
               transformers, switches, etc.), the testing agency
               technician shall provide written certification to
               the contractor and University of Maryland that the
               tested component is or is not suitable to be
               energized.  This document shall be the Contractor's
               authorization to/or not to energize the equipment.

               The above noted document shall be on a standard
               NETA form or approved substitution.

     E.   All test results shall be certified by an electrical
          engineer registered in the State of Maryland.  Each test
          report shall bear the signature and seal of the
          professional engineer who shall certify the data and
          conclusions presented therein.  The stamp and seal shall
          be affixed to the first page of the body of the Report,
          not a cover or title sheet.

1.14 EST FIRM'S LIABILITY INSURANCE

     A.   Responsibility for Damage Claims

          The testing firm shall indemnify and hold harmless and
          defend the University of Maryland and all its
          representatives form all suites, actions, or claims of
          any character brought on account of any injuries or
          damages sustained by any person or property including
          State property and State employees, agents or
          representatives in consequence of any work performed
          under this testing contract, either by the testing firm
          or any Sub-Contractor, or their employees, agents, or
          representatives.

     B.   Liability Insurance

          1.   The testing firm and/or any Sub-Contractor shall
               maintain such insurance as will protect him/her
               from claim under Workmen's Compensation Acts, by
               coverage with Insurance Companies acceptable to the
               State Insurance Commissioner for damages which may
               arise, from operations under this testing contract,
               whether such operations be by himself/herself or by
               any sub-contractor or anyone directly or indirectly
               employed by the testing firm.
     
          2.   He/she shall protect himself/herself and the state
               from any other claims.

          3.   The limits for Bodily Injury Liability shall not be
               less than $500,000/$1,000,000; that is, $500,000 is
               the limit for injury per occurrence and $1,000,000
               in the aggregate.  The minimum limit for Property
               Damage Liability shall be $500,000 per occurrence
               and $1,000,000 aggregate.

          4.   The above policies for Bodily Injury and Property
               Damage Liability Insurance shall be so written as
               to include Contingent Bodily Injury against claims
               from the operations of the Sub-Contractors.

          5.   Certificates of the testing firm's insurance
               containing evidence of the Hold Harmless Clause
               protecting the University of Maryland shall be
               filed with the Department of Architecture,
               Engineering & construction and shall be subject to
               their approval for adequacy of protection.

1.15 CHARGES

     A.   The charges for this testing contract shall be submitted
          on a monthly basis and shall be payable by the
          construction contractor on a monthly basis.  Invoices
          shall be separate, by project identification.

     B.   The hourly rate quoted for a two-person testing crew per
          hour shall include charge for administrative expenses,
          overhead expenses, vehicle mileage and profits.

          1.   The maximum allowable round trip travel time for
               any testing procedure anywhere in the state, shall
               be five (5) hours.

     C.   Site visits by the testing company shall be certified by
          either the on-job electrical contractor's foreman or by
          a responsible staff member of the using agency.  This
          certification on an approved form, shall be submitted
          with each job invoice and shall state the number of hours
          at the job site, travel time, and the names of the
          individuals doing the work.

16.16 Controls


PART 1 - GENERAL

1.01 SECTIONS INCLUDES

     A.   Control switches and stations.

     B.   Photocells.

     C.   Relays.

     D.   Time switches.

     E.   Control device enclosures.

1.02 SUBMITTALS

     A.   Shop Drawings:  Indicate control device enclosure wiring
          diagrams and panel layout drawings.

     B.   Product Data:  Provide data on each control device
          specified.

     C.   Operating and Maintenance Instructions:  Include
          instructions on adjusting, repairing, cleaning, and
          lubricating each control device specified.

PART 2 - PRODUCTS

2.01 CONTROL SWITCHES AND STATIONS

     A.   Description:  Heavy duty, oil-tight control switches and
          stations manufactured to NEMA ICS 2.

     B.   Contact Ratings:  Class A150.

2.02 PHOTOCELL SWITCH

     A.   Description:  Photocell switch manufactured to NEMA ICS
          2.

     B.   Ratings:  Contact Ratings:  Class A150.

     C.   Enclosure:  Gasketed, cast feralloy box with conduit hub.

2.03 RELAYS

     A.   Description:  Relays manufactured to NEMA ICS 2.

          1.   Magnetic Control Relay:  Class A300.

          2.   Time-Delay Relay:  Class A600.

     B.   Ratings: 

          1.   Contact Ratings:  Class A150.

          2.   Coil Voltage: 120 volts, 60 Hz., Single Phase.

     C.   Enclosure:  NEMA Type 1 for interior and NEMA type 4 for
          exterior use.

2.04 TIME SWITCH

     A.   Description:  Clock timer manufactured to NEMA ICS 2,
          with astronomical dial.

     B.   Ratings:

          1.   Contact Ratings:  Class A150; SPST.

          2.   Coil Voltage:  120 volts, 60 Hz., Single Phase.

          3.   Dial Time:  24 hours, 7 days.

     C.   Enclosure:  NEMA Type 1 for indoor applications, and NEMA
          Type 4 for outdoor applications.

2.05 CONTROL DEVICE ENCLOSURES

     A.   Description:  Shop fabricate and wire control device
          enclosures to NEMA ICS 1, for groupings of more than one
          device.

     B.   Use hinged cover enclosures under provisions of Section
          16110.

     C.   Terminal Blocks:  ANSI/NEMA ICS 4.

     D.   Fabrication:  Shop assemble to NEMA ICS 6.  Use plastic
          wiring through to route internal wiring.



PART 3 - EXECUTION

3.01 INSTALLATION

     A.   Install control devices in accordance with manufactures
          instructions.

     B.   Install individual components in enclosures.

     C.   Connect control devices to systems controlled, to achieve
          proper system operation.

3.02 ADJUSTING

     A.   Adjust time delay relays and clock timers to achieve
          specified system operation.

16.17 Security Camera Equipment


PART 1 - GENERAL

     This section applies to security cameras accessories and
     equipment.

1.01 SECTION INCLUDES

     A.   Pan-tilt-zoom telemetry controls.
     B.   Multiplexers.
     C.   VCR's.
     D.   Monitors.
     E.   Consoles and Playback Stations.
     F.   Wiring.

1.02 REGULATORY REQUIREMENTS

     A.   Furnished products shall be listed by Underwriters
          Laboratories. Inc.

     B.   All work shall conform to:

               1.   ANSI.
               2.   National Electric Code (NEC)
               3.   University of Maryland's Division 16 Electrical
                    Standards.

1.03 GENERAL REQUIREMENTS

     A.   Design, furnish and install the camera system equipment
          and layout in conformance with IES recommended
          procedures.  All CCTV system components are to be new,
          unused products provided with complete Manufacturer's and
          Contractor's warranty of no less than two years Parts and
          Labor  service.

     B.   Pan-tilt-zoom Telemetry Controls

          The telemetry control shall be an integral control
          function of the Video Multiplexer System.  Any individual
          camera site called by the Multiplexer Control; keyboard
          shall be controllable from the remote site.  A telemetry
          receiver shall be mounted in proximity to each camera
          location.  The telemetry receiver driver shall be
          enclosed in the environmental enclosure where necessary. 
          The telemetry receiver shall be powered by 24 VAC and
          shall incorporate DTMF telemetry protocol delivered via
          twisted pair SL/PP cable.  The receiver shall be a
          Dedicated Micros Model TRC1/024/01 or approved equal.

     C.   Video Multiplexing

          1.   The video multiplexers shall be 16 input color,
               full duplex devices.  They will allow for
               simultaneous time base corrected digital recording
               of all cameras to tape as full screen format. 
               Recording shall be accomplished in a field
               recording sampling method.  Sixteen images, one
               from each camera input shall be recorded in less
               than one second in the  real time' 24 hour mode on
               the specified VCR.

          2.   The multiplexer shall offer live selectable multi-
               screen displays while recording.  Displays shall be
               full quad 3x3, 4x4, or 8 plus 2 on the Main
               Monitor.  The secondary or spot monitor shall be
               full live screen video from any selected camera or
               shall offer sequencing video from selected cameras. 
               The multiplexer shall provide a digital freeze
               frame and a x2 electronic zoom in full screen, in
               live and playback modes, and have the ability to
               digitally  scan' each field of the video.  The
               multiplexer shall feature an adjustable field delay
               schedule for compatibility with virtually any VCR.

          3.   The unit shall feature programmable, digital
               activity detection on all video channels.  Digital
               activity detection shall provide two selectable
               modes of operation: exclusive and interleave.  The
               exclusive mode of activity detection shall record
               cameras showing only activity, while recording
               fewer of the non-active cameras. 

          4.   The multiplexer shall be capable of a telemetry
               control of up to sixteen (16) pan-tilt-zoom cameras
               when utilizing the  telemetry control adaptor
               TAD1/012 at each multiplexer CPU.  Telemetry data
               can be distributed in a serial fashion to each TRC2
               Receiver driver in the system.  The multiplexer
               shall be a Dedicated Micros Uniplex Series 2 Model
               DM/UPX2/D/N/C or approved equal.  

          5.   The multiplexers will use a MC04 Multiport
               Controller so that one operator may control two (2)
               to four (4) multiplexers using a single KBU2
               Control Keyboard.  The control keyboard, output
               monitors, and VCR will be located remotely from the
               Multiplexer CPU.  Remote control of the CPU's will
               be accomplished by the use of the KA01 Keyboard
               Adaptor and a pair of RS232 Line Drivers, such as
               Black Box Model ME-800A or approved equal.

          6.   All video communications between the CPU's, the
               VCR's, and the monitors will be transmitted via
               VTTI Model VTT-7000 Video Transceivers or approved
               equal. 

     D.   VCR's

          Each VCR will be a time lapse VCR with  virtual real
          time' recording capability of 18, fields/seconds in 24
          hour mode as well as additional recording durations of 2,
          6, 12, 24, 48, 72, 120, and 168 hour record modes.  The
          VCR shall have a resolution of 300 lines in color, 350
          lines in monochrome.  The VCR shall have a high-speed
          rewind mechanism to rewind in less than 100 seconds. 
          Search function by time, date, and alarm may be
          accomplished.  The unit shall have a four mode
          job/shuttle search controller.  The VCR shall be the
          Toshiba Model KV-7168.  The VCR's shall be rack mounted
          in a 19" console with a Pelco RM-6010 Mount Kit.  

     E.   Monitors

          Each multiplexer will be equipped with both a main and a
          spot monitor.  These color monitors are to have 19"
          diagonal viewing areas.  Resolution shall be over 400 TV
          lines.  Audio inputs, speakers, and looping BNC video
          inputs are to be available.  Separate S-VHS inputs will
          be available for future requirements.  The monitors shall
          be  Toshiba Model CM1900K Monitors or approved equal. 
          Monitors are to be mounted as requested by the
          University.
     
     F.   Console and Playback Stations

          1.   When necessary a complete security console with
               provisions to rack mount all recording, control,
               and display equipment will be provided for.

          2.   When necessary, a complete playback station will be
               provided.  This work station will consist of a
               DM/UPX2/S/EM Color Simplex Multiplexer, KBU2
               Keyboard, and Toshiba KV-7168 TL VCR and Toshiba
               CM1900K 19" Color Monitor or approved equals.  The
               playback/review station may also include a Toshiba
               6A Printer Model HC 1200A or approved equal.  The
               printer must also use print paper model HCA-AGN or
               approved equal. This system shall allow for the
               offline review of any archived recorded video from
               the System with selectable, individual playback of
               multiplexed cameras.

     G.   Wiring

          The Contractor is responsible to make all camera
          locations function properly over the University supplied
          24 AWG gauge twisted copper pair cabling provided.  The
          Contractor shall take into account distances involved and
          the copper twisted pair cable specifications listed below
          and supply the necessary equipment to make each camera
          installation function properly.

          All equipment supplied must be compatible with existing
          wiring.
 
          1.   Existing Station Copper Cable

               a.   All unshielded twisted pair (UTP) station
                    copper cable supporting voice communications
                    requirement is AT&T and meets the following
                    technical specifications:

          Gauge:                        24AWG
          Outside Diameter:             0.17 in (4.3 mm)
          Insulation:                   PVC (1010) or ECTFE (2010)
          Maximum DC Resistance:        28.6 Ohms/1000 ft.
          Nominal Mutual Capacitance:   20 nF/1000 ft @ 1 kHz
          Characteristic Impedance      100 Ohms +/- 15% @ 1-16 Mhz

               b.   All UTP station copper cable supporting data
                    communications is AT&T and meets the following
                    technical specifications:

          Gauge:                        24 AWG
          Outside Diameter:             0.17 in (4.3 mm)
          Insulation:                   PVC (1061) or Teflon (2061)
          Maximum DC Resistance:        28.6 Ohms/1000 ft.
          Nominal Mutual Capacitance:   14 nF/1000 ft @ 1 kHz
          Attenuation:                  6 dB/1000 ft @ 1 kHz
          Characteristic Impedance      100 Ohms +/- 15% @ 1-16 Mhz

               c.   All copper cable and jumpers conform to REA
                    color guide and meet NEC articles 725-38, 3
                    (B) 1, 2, and 3.

          2.   Existing Riser Copper Cable

               All UTP riser copper cable supporting voice and
               data communications is standard 24 gauge, paired
               dual, semi-rigid PVC skin over foamed PE, AT&T, and
               meets the following technical specifications:

          Gauge:                        24 AWG, solid copper
                                        conductor, twisted pair
          DC Resistance:                25.7 Ohms/1000 ft
          Mutual Capacitance:           15.8 pF/ft
          Characteristic Impedance:     100 Ohms @ 1 kHz 
                                        105 Ohms @ 1 Mhz
          Attenuation:                  6.25 dB/1000 ft @ 1 Mhz

          3.   Existing Underground Copper Cable

               All underground copper cable supporting voice and
               data communications is standard 24 gauge, paired
               dual- insulated , with foam skin and plastic ,
               surrounded by FLEXGEL filling compound, AT&T, and
               meets the following technical specifications:

          Gauge:                        24 AWG, solid copper
                                        conductor
          DC Resistance:                27.3 Ohms/1000 ft
          Mutual Capacitance:           15.7 pF/ft
          Characteristic Impedance:     100 Ohms @ 1 kHz 
          Attenuation:                  6.25 dB/1000 ft @ 1 Mhz

1.04 QUALIFICATIONS

     Manufacturer:  Company specializing in manufacturing products
     specified in this section with minimum five years experience.

1.05 PROJECT RECORD DOCUMENTS

     Accurately record actual locations of each camera with the
     switching arrangements.

PART 2 - PRODUCTS

2.01 EXTERIOR EQUIPMENT AND ACCESSORIES

     Equipment supplied shall be compatible with existing
     equipment.

2.02 CAMERA EQUIPMENT AND ACCESSORIES

     A.   Internal Wiring:  Component wiring within enclosures
          shall be UL Listed.

     B.   Labels:  All fixtures shall bear UL Wet Location and
          I.B.E.W. labels.  

2.03 SPLICES, TAPS

     A.   All splices underground in handholes or other wet
          locations shall be waterproof and made with Scotchcast 85
          Multi-Mold Splicing Kits, or approved equal.

     B.   All taps shall use suitable connectors such as Burndy
          Type Ks and taped with two layers of 3M Scotch Brand or
          approved equal rubber tape and six layers of vinyl
          plastic electrical tape. 

     C.   Splices in handholes shall be supported on bricks 8
          inches above the bottom of the handhole.  Slices shall be
          kept to a minimum and are prohibited in locations other
          then handholes, pullboxes or lighting unit bases, except
          for the purposes of retaining circuity of any existing
          underground wiring where existing poles or wiring are
          distributed.


PART 3 - EXECUTION

3.01 EXAMINATION AND PREPARATION

     A.   Examine adjacent surfaces to determine that surfaces are
          ready to receive work.

     B.   Examine each piece of equipment to determine suitability
          for location specified.

3.02 INSTALLATION

     A.   Install camera equipment and accessories in accordance
          with manufacturers instructions.

          1.   Install equipment in consoles.

          2.   Connect equipment to the branch circuits and cables
               provided by university or Contractor.

          3.   Bond products and metal accessories to the branch
               circuit equipment grounding conductor.

     B.   Equipment shall be located clear of exit signs, speakers,
          smoke detectors, pipes, ducts, and other mounted
          equipment. 

     C.   Open trenches shall be limited to 30 linear feet before
          backfilling.

3.03 ADJUSTING AND CLEANING

     A.   Adjust equipment as directed by the University.

     B.   Clean paint splatters, dirt, and debris from installed
          equipment.

     C.   Touch up enclosures, buildings, and interior finish at
          completion of work.

     D.   Replace equipment and mounts which have failed at
          completion of work.

3.04 COORDINATION

     A.   Confirm compatibility and interface of other materials
          with CCTV system.  Report discrepancies to the
          University.

     B.   Supply trim rings, backboxes, etc. to other trades as
          necessary.

     C.   Coordinate with Division 15 to avoid conflicts between
          cameras, supports, fittings, and mechanical equipment.

     D.   Before ordering, confirm construction details and
          architectural finish for each area.

3.05 ACCEPTANCE

     A.   Contractor shall demonstrate to the satisfaction of the
          University that all equipment is operating properly.  Any
          faulty equipment shall be replaced at the Contractor's
          expense.  The Contractor shall demonstrate operation of
          all installed equipment.

16.18 Security Cameras (Exterior)


PART 1 - GENERAL

     This section applies to exterior and parking garage security
     cameras.

1.01 SECTION INCLUDES

     A.   Exterior Cameras and accessories.

     B.   Poles and brackets.

1.02 REGULATORY REQUIREMENTS

     A.   Furnished products shall be listed by Underwriters
          Laboratories. Inc.

     B.   All work shall conform to:
     
          1.    ANSI.

          2.   National Electric Code (NEC)

          3.   University of Maryland's Division 16 Electrical
               Standards.
     
1.03 GENERAL REQUIREMENTS

     A.   Design, furnish and install the exterior camera system
          layout in conformance with IES recommended procedures and
          foot candle requirements as specified below.  All
          exterior cameras shall be 120 VAC stepped down to 24 VAC.
          All CCTV system components are to be new, unused products
          provided with complete Manufacturer's and Contractor's
          warranty of no less than two years Parts and Labor
          complete service.

     B.   Cameras

          The camera shall be a 1/3 inch format interline transfer
          CCD, color camera.  The camera shall have a 380,000 pixel
          array producing 480 lines horizontal resolution with 50db
          signal/noise ratio.  Sensitivity shall be a minimum of 2
          lux.  The camera shall include auto back light
          compensation circuitry.  It shall accept C mount optics
          to accommodate the zoom lens required.  The camera shall
          be a Panasonic  WV-CP614 or approved equal.  For areas
          with low levels of lighting or other darkening conditions
          consideration will be given to using a different dual
          scan technology camera.
     
     C.   Lens

          Lens-1 (Harris Domed Sites), the complete
          camera/lens/connector package must be compact enough to
          fit internally into the Environmental Dome.  The zoom
          lens shall be a 10x auto-iris with a minimum focal length
          of 8.5-51MM.  The lens shall include an integral spot
          filter.  Mechanical dimensions shall be such that the
          lens and camera combination will fit in the enclosure.  
          The lens shall include a preset position potentiometer. 
          
          Lens-2 (Free Standing Code Blue Sites), the complete
          camera/lens/connector package must be compact enough to
          fit internally to the Free Standing Code Blue Telephone
          enclosure which are approximately 11" in diameter.  The
          zoom lens shall be a 6x auto-iris with a minimum focal
          length of 8.5-51MM.  The lens shall include an integral
          spot filter.  Lens includes a preset position
          potentiometer.

          Lens-3 (Legacy Series Environmental enclosured Sites),
          the complete camera/lens/connector package must be
          compact enough to fit internally into the Environmental
          Enclosure.  The zoom lens shall be a 10x auto-iris with
          a minimum focal length of 8.5-51MM.  The lens shall
          include an integral spot filter. The lens shall include
          a preset position potentiometer.  

     D.   Environmental Enclosures

          All exterior camera sites are to be configured in an
          environmental enclosure which incorporates a 360 degree
          rotation  pan and tilt devise to allow for camera viewing
          in all directions from the camera site location.  Two
          types of environmental enclosures shall be utilized.

          Enclosure-1  The Harris Dome enclosure.  The enclosure
          shall incorporate a 20" lower hemisphere with a black  
          opaque lower dome with a clear viewing slot. The 
          environmental dome shall include factory installed
          heater,blower, and service light.  The service light
          shall automatically come on when the lower dome is
          opened. The dome is to be powered by 110 VAC.  The
          integral pan-tilt will be pre-wired for all system
          functions.  The environmental dome shall be the Pelco 
          ED-2820-SL/PP or approved equal.  Pan-tilt includes preset
          position potentiometer.

          Enclosure-2 Legacy Series Enclosure.  The enclosure is to
          be powered by 110 VAC.  The enclosure will be pre-wired
          for all system functions.  The environmental enclosure
          shall include factory installed heater. This heated
          enclosure system shall be a Pelco Model EH4718L-2 with a
          PT480-24P/PP (pan & tilt), SS4718L (sun shroud), and a
          PM-4010 (mount)or approved equal.

     E.   Mounts

          An appropriate mounting device will be provided at all
          camera locations to provide a stable and accessible means
          of access to the camera site.  The specifics of each site
          location will be determined by local considerations at
          the indicated mounting location during the site walk-
          through.  When domes are mounted to buildings, parapet
          mounts, which incorporate swinging arms for
          serviceability, shall be provided.  Whenever possible,
          domes are preferred to be roof mounted as opposed to wall
          mounted, for maximum serviceability.  Typical building
          mounts shall be Pelco PP200 parapet mounts with Pelco
          PP1200 adaptor/rotation devices or approved equal.  Where
          pole mounted, the mounts shall be Pelco PA102 pole
          adaptors with Pelco ST-1 support struts and Pelco SPA-102
          pole mounts or approved equal.  Where corner mounts are
          to be used, the mount shall be Pelco CM100 or approved
          equal.  Other mounts are to be applied where required. 

     F.   Lighting

          Contractor will assure that adequate area lighting exists
          to allow for the proper viewing of the video images in
          the viewing area.  This may be accomplished by use of the
          appropriate combination of cameras, lenses, environmental
          enclosures, and mounts, as well as, the possible addition
          of exterior lights.  Metal Halide is the preferred
          exterior lighting source.
 
     G.   Parking Garage

          Cameras installed within parking garages will conform to
          the general requirements listed above for cameras,
          lenses, environmental enclosures, mounts and lighting.

1.04 REFERENCES

     A.   Poles - Shall conform to University of Maryland standard
          poles or PERT Telephone (Police Emergency Reporting
          Telephone) Installation Criteria 4.15.97 for Free
          Standing Code Blue Phones with Camera Extensions. 



     B.   Building exterior - Shall be a mountable surface capable
          of bearing a shear weight of 100 lbs.

1.05 QUALIFICATIONS

     A.   Manufacturer:  Company specializing in manufacturing
          products specified in this section with minimum five
          years experience.

1.06 PROJECT RECORD DOCUMENTS

     A.   Accurately record actual locations of each camera with
          the switching arrangements.


PART 2 - PRODUCTS

2.01 EXTERIOR ARCHITECTURAL CAMERAS AND ACCESSORIES

     A.   Environmental enclosures, complete with gaskets to form
          weatherproof assembly.

     B.   Low temperature operation to zero degrees Fahrenheit.

     C.   Camera enclosure shall be vandal-proof.

     E.   Transceivers supplied shall be compatible with existing
          equipment.

     F.   Camera's mounted on parapets must not be mounted on false
          parapets.

2.02  EXTERIOR CAMERAS AND ACCESSORIES

     General Description: 

     A.   Internal Wiring:  Component wiring within enclosures
          shall be UL Listed.

     B.   Enclosure Exterior Finish: Shall be aluminum with
          polyester powder finish and an Acrylic or Polycarbonate
          viewing cover. 

     C.   Labels:  All fixtures shall bear UL Wet Location and
          I.B.E.W. labels.  
     
2.03 POLES

     A.   Poles shall be compatible with other University Standard
          Poles.
     
     B.   Free Standing Code Blue Phone Camera Mounts shall be
          compatible with the Code Blue equipment.
          
2.04 SPLICES, TAPS

     A.   All splices underground in handholes or other wet
          locations shall be waterproof and made with Scotchcast 85
          Multi-Mold Splicing Kits, or approved equal.

     B.   All Taps in pole bases shall use suitable connectors such
          as Burndy Type Ks and taped with two layers of 3M Scotch
          Brand or approved equal rubber tape and six layers of
          vinyl plastic electrical tape.  Tap wiring to the
          luminaire shall incorporate a Bus type HEB waterproof 
          in-line fuseholder with this as recommended by the ballast
          manufacturer and #12 XHHW conductors.

     C.   Splices in handholes shall be supported on bricks 8
          inches above the bottom of the handhole.  Slices shall be
          kept to a minimum and are prohibited in locations other
          then handholes, pullboxes or lighting unit bases, except
          for the purposes of retaining circuity of any existing
          underground wiring where existing poles or wiring are
          distributed.


PART 3 - EXECUTION

3.01 EXAMINATION AND PREPARATION

     A.   Examine adjacent surfaces to determine that surfaces are
          ready to receive work.

     B.   Examine each camera, lens, and mount to determine
          suitability for location specified.

3.02 INSTALLATION

     A.   Install cameras and accessories in accordance with
          manufacturers instructions.

          1.   Install external cameras in enclosures.

          2.   Connect cameras units to the branch circuits and
               cables provided by Contractor.

          3.   Bond products and metal accessories to the branch
               circuit equipment grounding conductor.

     B.   Cameras shall be located clear of exit signs, speakers,
          smoke detectors, pipes, ducts, and other mounted
          equipment. 

     C.   Open trenches shall be limited to 30 linear feet before
          backfilling.

3.03 ADJUSTING AND CLEANING

     A.   Align cameras, clean lenses and view ports at completion
          of work.

     B.   Aim adjustable cameras as directed by the University.

     C.   Clean paint splatters, dirt, and debris from installed
          cameras and enclosures.

     D.   Touch up enclosures, buildings and pole finish at
          completion of work.

     E.   Replace cameras, lenses, enclosures, and mounts which
          have failed at completion of work.

3.04 COORDINATION

     A.   Confirm compatibility and interface of other materials
          with CCTV system.  Report discrepancies to the
          University.

     B.   Supply trim rings, backboxes, etc. to other trades as
          necessary.

     C.   Coordinate with Division 15 to avoid conflicts between
          cameras, supports, fittings, and mechanical equipment.

     D.   Before ordering, confirm construction details and
          architectural finish for each area.

3.05 ACCEPTANCE

     A.   Contractor shall demonstrate to the satisfaction of the
          University that all cameras, lenses, and enclosures are
          operating properly.  Any faulty equipment shall be
          replaced at the Contractor's expense.  The Contractor
          shall demonstrate operation of all installed equipment.

16.19 Security Cameras (Interior)


PART 1 - GENERAL

     This section applies to interior security cameras.

1.01 SECTION INCLUDES

     A.   Interior Cameras and accessories.

     B.   Brackets.

1.02 REGULATORY REQUIREMENTS

     A.   Furnished products shall be listed by Underwriters
          Laboratories. Inc.

     B.   All work shall conform to:

               1.   ANSI.
               2.   National Electric Code (NEC)
               3.   University of Maryland's Division 16 Electrical
                    Standards.
     
1.03 GENERAL REQUIREMENTS

     A.   Design, furnish and install the interior camera system
          layout in conformance with IES recommended procedures. 
          All interior cameras shall be 120 VAC stepped down to 24
          VAC. All system components are to be new, unused products
          provided with complete Manufacturer's and Contractor's
          warranty of no less than two years Parts and Labor
          service.

     B.   Cameras

          The camera shall be a 1/2 inch format interline transfer
          CCD, color camera.  The camera shall have a 410,000 pixel
          array producing 470 lines horizontal resolution with 48db
          signal/noise ratio.  Sensitivity shall be a minimum of 2
          lux.  The camera shall include auto back light
          compensation circuitry.  It shall accept C mount optics
          to accommodate the zoom lens required.  The camera shall
          be a Toshiba Model IL-642A or approved equal.  For areas
          with low levels of lighting or other darkening conditions
          consideration will be given to using a different camera. 
          Recommendations are to be submitted to the University for
          approval.

     C.   Lens

          Lens-1 the complete camera/lens/connector package must be
          compact enough to fit internally into the vandal
          resistant enclosure.  The zoom lens shall be a 10x auto-
          iris with a minimum focal length of 8.5-51MM.  The lens
          shall include an integral spot filter.  Mechanical
          dimensions shall be such that the lens and camera
          combination will fit in the enclosure.   The lens shall
          include a preset position potentiometer.

     D.   Vandal Resistant Enclosures

          All interior camera sites are to be configured in a
          vandal resistant enclosure which incorporates a 360
          degree rotation  pan and tilt devise to allow for camera
          viewing in all directions from the camera site location. 

          1.   Enclosure-1  The Harris Dome enclosure.  The
               enclosure shall incorporate a 20" lower hemisphere
               with a black opaque lower dome with a clear viewing
               slot.  The environmental dome shall include factory
               installed heater, blower, and service light if
               necessary.  The service light shall automatically
               come on when the lower dome is opened. The dome is
               to be powered by 110 VAC.  The integral pan-tilt
               will be pre-wired for all system functions.  The
               environmental dome shall be the Pelco ED-2820-SL/PP
               or approved equal.  Pan-tilt includes preset
               position potentiometer.

          2.   Enclosure-2 Covert Enclosure.  The enclosure is to
               be powered by 110 VAC.  The enclosure will be pre-
               wired for all system functions. Covert enclosures
               are too numerous to specifically describe and will
               be sized and shaped to fit with a specific need
               within a building (for example exit sign enclosure,
               emergency lighting enclosure, two way mirror
               enclosure, etc.).

     E.   Mounts

          An appropriate mounting device will be used at all camera
          locations to provide a stable and accessible means of
          access to the camera site.  The specifics of each site
          location will be determined by local considerations at
          the indicated mounting location during the site walk-
          through.  All mounts shall be rated at a minimum of 50
          pounds more than the total dead load weight of all
          attachments. 

     F.   Lighting

          Contractor will assure that adequate area lighting exists
          to allow for the proper viewing of the video images in
          the viewing area.  This may be accomplished by use of the
          appropriate combination of cameras, lenses, vandal
          resistant  enclosures, and mounts, as well as, the
          possible addition of interior lights. 

1.04 QUALIFICATIONS

     Manufacturer:  Company specializing in manufacturing products
     specified in this section with minimum five years experience.

1.05 PROJECT RECORD DOCUMENTS

     Accurately record actual locations of each camera with the
     switching arrangements.

PART 2 - PRODUCTS

2.01 EXTERIOR ARCHITECTURAL CAMERAS AND ACCESSORIES

     A.   Camera enclosure shall be vandal-proof.

     B.   Transceivers supplied shall be compatible with existing
          equipment.

2.02 INTERIOR CAMERAS AND ACCESSORIES

     A.   Internal Wiring:  Component wiring within enclosures
          shall be UL Listed.

     B.   Enclosure Exterior Finish: Shall be aluminum with
          polyester powder finish and an Acrylic or Polycarbonate
          viewing cover. 

     C.   Labels:  All fixtures shall bear UL Wet Location and
          I.B.E.W. labels.

2.03 SPLICES, TAPS

     A.   All splices underground in handholes or other wet
          locations shall be waterproof and made with Scotchcast 85
          Multi-Mold Splicing Kits, or approved equal.
     
     B.   All taps shall use suitable connectors such as Burndy
          Type Ks and taped with two layers of 3M Scotch Brand or
          approved equal rubber tape and six layers of vinyl
          plastic electrical tape. 

     C.   Splices in handholes shall be supported on bricks 8
          inches above the bottom of the handhole.  Slices shall be
          kept to a minimum and are prohibited in locations other
          then handholes, pullboxes or lighting unit bases, except
          for the purposes of retaining circuity of any existing
          underground wiring where existing poles or wiring are
          distributed.

PART 3 - EXECUTION

3.01 EXAMINATION AND PREPARATION

     A.   Examine adjacent surfaces to determine that surfaces are
          ready to receive work.

     B.   Examine each camera, lens, and mount to determine
          suitability for location specified.

3.02 INSTALLATION

     A.   Install cameras and accessories in accordance with
          manufacturers instructions.
          
          1.   Install interior cameras in enclosures.

          2.   Connect cameras units to the branch circuits and
               cables provided by Contractor.

          3.   Bond products and metal accessories to the branch
               circuit equipment grounding conductor.

     B.   Cameras shall be located clear of exit signs, speakers,
          smoke detectors, pipes, ducts, and other mounted
          equipment. 

     C.   Open trenches shall be limited to 30 linear feet before
          backfilling.

3.03 ADJUSTING AND CLEANING

     A.   Align cameras, clean lenses and view ports at completion
          of work.

     B.   Aim adjustable cameras as directed by the University.

     C.   Clean paint splatters, dirt, and debris from installed
          cameras and enclosures.

     D.   Touch up enclosures, buildings and interior finish at
          completion of work.

     E.   Replace cameras, lenses, enclosures, and mounts which
          have failed at completion of work.

3.04 COORDINATION

     A.   Confirm compatibility and interface of other materials
          with system.  Report discrepancies to the University.

     B.   Supply trim rings, backboxes, etc. to other trades as
          necessary.

     C.   Coordinate with Division 15 to avoid conflicts between
          cameras, supports, fittings, and mechanical equipment.

     D.   Before ordering, confirm construction details and
          architectural finish for each area.

3.05 ACCEPTANCE

     Contractor shall demonstrate to the satisfaction of the
     University that all cameras, lenses, and enclosures are
     operating properly.  Any faulty equipment shall be replaced at
     the Contractor's expense.  The Contractor shall demonstrate
     operation of all installed equipment.